Specifications Table for RQYQ-P

RQYQ140PY1 RQYQ8PY1B RQYQ10PY1B RQYQ12PY1B RQYQ14PY1B RQYQ16PY1B RQYQ18PY1 RQYQ20PY1 RQYQ22PY1 RQYQ24PY1 RQYQ26PY1 RQYQ28PY1 RQYQ30PY1 RQYQ32PY1 RQYQ34PY1 RQYQ36PY1 RQYQ38PY1 RQYQ40PY1 RQYQ42PY1 RQYQ44PY1 RQYQ46PY1 RQYQ48PY1
System Outdoor unit module 1   RQYQ140P RQYQ8P RQYQ10P RQYQ12P RQYQ14P RQYQ16P RQYQ8P RQYQ8P RQYQ10P RQYQ12P RQYQ10P RQYQ12P RQYQ14P RQYQ16P RQYQ10P RQYQ10P RQYQ10P RQYQ12P RQYQ10P RQYQ12P RQYQ14P RQYQ16P
  Outdoor unit module 2               RQYQ10P RQYQ12P RQYQ12P RQYQ12P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ10P RQYQ10P RQYQ12P RQYQ12P RQYQ16P RQYQ16P RQYQ16P RQYQ16P
  Outdoor unit module 3                               RQYQ14P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P
Recommended combination 4 x FXSQ32A2VEB
Cooling capacity Prated,c kW 14
  Nom. 35°CDB kW 14.0 (1) 22.4 (1) 28.0 (1) 33.5 (1) 40.0 (1) 45.0 (1) 50.4 (1) 55.9 (1) 61.5 (1) 67.0 (1) 73.0 (1) 78.5 (1) 85.0 (1) 90.0 (1) 96.0 (1) 101 (1) 107 (1) 112 (1) 118 (1) 124 (1) 130 (1) 135 (1)
Heating capacity Prated,h kW 16
  Nom. 6°CWB kW 16 25 31.5 (2) 37.5 (2) 45 50 56.5 (2) 62.5 (2) 69 75 81.5 (2) 87.5 (2) 95 100 (2) 108 (2) 113 (2) 119 (2) 125 (2) 132 (2) 138 (2) 145 (2) 150 (2)
EER at nom. capacity 35°CDB KW/KW 4.17 4.27 3.66 3.32 3.45 3.31 3.91 3.63 3.46 3.32 3.43 3.31 3.37 3.31 3.57 3.49 3.41 3.31 3.38 3.51 3.35 3.31
Space cooling A Condition (35°C - 27/19) EERd   2.54
    Pdc kW 14.0
  B Condition (30°C - 27/19) EERd   4.40
    Pdc kW 10.3
  C Condition (25°C - 27/19) EERd   7.31
    Pdc kW 6.63
  D Condition (20°C - 27/19) EERd   9.29
    Pdc kW 5.01
Space heating (Average climate) TBivalent COPd (declared COP)   1.92
    Pdh (declared heating cap) kW 8.5
    Tbiv (bivalent temperature) °C -10
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)   1.92
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW 8.5
  A Condition (-7°C) COPd (declared COP)   2.20
    Pdh (declared heating cap) kW 7.52
  B Condition (2°C) COPd (declared COP)   3.42
    Pdh (declared heating cap) kW 4.58
  C Condition (7°C) COPd (declared COP)   4.84
    Pdh (declared heating cap) kW 3.29
  D Condition (12°C) COPd (declared COP)   6.43
    Pdh (declared heating cap) kW 4.18
Capacity range HP 5 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Maximum number of connectable indoor units 10 17 21 26 30 34 39 43 47 52 56 60 64 64 64 64 64 64 64 64 64 64
Indoor index connection Min.   62.5 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600
  Nom.   125 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
  Max.   162.5 260 325 390 455 520 585 650 715 780 845 910 975 1040 1105 1170 1235 1300 1365 1430 1495 1560
Dimensions Unit Height mm 1680 1680 1680 1680 1680 1680
    Width mm 635 930 930 930 1240 1240
    Depth mm 765 765 765 765 765 765
Weight Unit kg 175 230 284 284 381 381
Fan Air flow rate Cooling Nom. m³/min 95 180 185 200 233 233
  External static pressure Max. Pa 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5
    Max. °CDB 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43
  Heating Min. °CWB -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20
    Max. °CWB 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5
Sound power level Cooling Nom. dBA 79
Sound pressure level Cooling Nom. dBA   57 58 60 60 60 61 62 63 63 63 63 63 63 64 64 65 65 65 65 65 65
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
  GWP   2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5 2087.5
  Charge tCO2Eq 23.2 22.5 24.4 24.4 24.4 24.4
  Charge kg 11.1 10.8 11.7 11.7 11.7 11.7
Piping connections Liquid Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
    OD mm 9.52 9.52 9.52 12.7 12.7 12.7 15.9 15.9 15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
  Gas Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
    OD mm 15.9 19.1 22.2 28.6 28.6 28.6 28.6 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3 41.3
  Total piping length System Actual m 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300
  Level difference OU - IU Outdoor unit in highest position m 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
      Indoor unit in highest position m 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
    IU - IU Max. m 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Standard Accessories Installation manual Installation manual Installation manual Installation manual Installation manual Installation manual Installation manual
  Operation manual Operation manual Operation manual Operation manual Operation manual Operation manual Operation manual
  Clamps Clamps Clamps Clamps Clamps Clamps Clamps
  Connection pipes   Connection pipes Connection pipes Connection pipes Connection pipes Connection pipes
Power supply Name   Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - TOCA means the total value of each OC set. (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - MSC means the maximum current during start up of the compressor (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set. (4) - TOCA means the total value of each OC set.
  (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor (5) - MSC means the maximum current during start up of the compressor
  (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Select wire size based on the value of MCA or TOCA. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%.
  (8) - Select wire size based on the larger value of MCA or TOCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA
  (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases
  (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases