Specifications Table for RWEYQ-T9

RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ14T9Y1B RWEYQ16T9Y1B RWEYQ18T9Y1B RWEYQ20T9Y1B RWEYQ24T9Y1B RWEYQ26T9Y1B RWEYQ28T9Y1B RWEYQ22T9Y1B RWEYQ30T9Y1B RWEYQ32T9Y1B RWEYQ34T9Y1B RWEYQ36T9Y1B RWEYQ38T9Y1B RWEYQ40T9Y1B RWEYQ42T9Y1B
Sound pressure level Cooling Nom. dBA 48.0 (10) 50.0 (10) 56.0 (10) 58.0 (10) 51.0 (10) 52.0 (10) 53.0 (10) 59.0 (10) 60.0 (10) 61.0 (10) 57.0 (10) 55.0 (10) 58.0 (10) 60.0 (10) 61.0 (10) 62.0 (10) 62.0 (10)
Standard Accessories Installation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Water supply piping with strainer 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Capacity range HP 8 10 12 14 16 18 20 24 26 28 22 30 32 34 36 38 40 42
ηs,c % 326.8 307.8 359.0 330.7 307.6 308.7 298.1 342.6 322.5 306.1 311.3 308.3 318.2 342.5 352.3 338.8 341.4
Maximum number of connectable indoor units 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7) 64 (7)
Space cooling B Condition (30°C - 27/19), cooling tower (inlet/outlet) 26/* EERd % 6.9 6.3 7.0 6.3 6.5 6.5 6.3 7.0 6.6 6.3 6.6 6.3 6.5 6.7 7.0 6.7 6.5
    Pdc kW 16.5 20.6 24.7 29.5 33.0 37.1 41.3 49.4 54.2 58.9 45.3 61.9 66.0 70.0 74.1 78.8 83.6
  A Condition (35°C - 27/19), cooling tower (inlet/outlet) 30/35 Pdc kW 22.4 28.0 33.5 40.0 44.8 50.4 56.0 67.0 73.5 80.0 61.5 84.0 89.5 95.0 100.5 107.0 113.5
    EERd % 5.6 4.6 5.4 4.2 5.1 5.0 4.6 5.4 4.9 4.5 5.0 4.6 4.9 5.1 5.4 5.0 4.7
  D Condition (20°C - 27/19), cooling tower (inlet/outlet) 18/* Pdc kW 7.9 7.9 8.2 8.4 9.4 10.6 11.8 14.1 15.5 16.8 13.0 17.7 18.8 20.0 21.2 22.5 24.5
    EERd % 11.9 12.3 14.9 15.6 11.0 10.1 9.9 11.5 10.8 10.2 9.4 11.6 11.2 13.5 13.1 12.8 15.4
  C Condition (25°C - 27/19), cooling tower (inlet/outlet) 22/* EERd % 10.1 9.1 10.5 9.4 9.0 9.5 9.1 10.5 9.9 9.4 9.8 9.1 9.6 10.1 10.5 10.1 9.7
    Pdc kW 10.6 13.3 15.9 18.9 21.2 23.9 26.5 31.7 34.8 37.9 29.1 39.8 42.4 45.0 47.6 50.7 53.8
SCOP 13.3 11.8 11.1 10.1 11.7 12.5 11.9 11.1 10.4 9.9 11.4 11.9 11.6 11.4 11.2 10.7 10.3 10.0
Compressor Type   Hermetically sealed scroll inverter compressor Hermetically sealed scroll inverter compressor Hermetically sealed scroll inverter compressor Hermetically sealed scroll inverter compressor
Weight Unit kg 195 195 197 197
Refrigerant Charge TCO2Eq 16.5 16.5 20.0 20.0
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge kg 7.9 7.9 9.6 9.6
  Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
System Outdoor unit module 2           RWEYQ8T RWEYQ10T RWEYQ10T RWEYQ12T RWEYQ14T RWEYQ14T RWEYQ12T RWEYQ10T RWEYQ10T RWEYQ12T RWEYQ12T RWEYQ12T RWEYQ14T
  Outdoor unit module 3                         RWEYQ10T RWEYQ12T RWEYQ12T RWEYQ12T RWEYQ14T RWEYQ14T
  Outdoor unit module 1           RWEYQ8T RWEYQ8T RWEYQ10T RWEYQ12T RWEYQ12T RWEYQ14T RWEYQ10T RWEYQ10T RWEYQ10T RWEYQ10T RWEYQ12T RWEYQ12T RWEYQ12T
Indoor index connection Min.   100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 325.0 350.0 275.0 375.0 400.0 425.0 450.0 475.0 500.0
  Max.   300.0 375.0 450.0 525.0 600.0 675.0 750.0 900.0 975.0 1,050.0 825.0 1,125.0 1,200.0 1,275.0 1,350.0 1,425.0 1,500.0
Cooling capacity Prated,c kW 22.4 (1) 28.0 (1) 33.5 (1) 40.0 (1) 44.8 (1) 50.4 (1) 56.0 (1) 67.0 (1) 73.5 (1) 80.0 (1) 61.5 (1) 84.0 (1) 89.5 (1) 95.0 (1) 100.5 (1) 107.0 (1) 113.5 (1)
Recommended combination 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 8 x FXMQ63P7VEB 12 x FXMQ50P7VEB 7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 12 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB 12 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 18 x FXMQ50P7VEB 13 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 8 x FXMQ50P7VEB + 10 x FXMQ63P7VEB 3 x FXMQ50P7VEB + 15 x FXMQ63P7VEB
Space heating (Average climate) TOL COPd (declared COP)   7.2 6.1 5.8 5.8 6.1 6.6 6.2 5.8 5.3 4.9 6.0 6.2 6.1 5.9 5.8 5.4 5.1
    Pdh (declared heating cap) kW 25.0 31.5 37.5 45.0 50.0 56.5 63.0 75.0 82.5 90.0 69.0 94.5 100.5 106.5 112.5 120.0 127.5
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW 8.9 8.8 8.8 9.2 8.6 8.7 9.6 11.5 12.7 13.9 10.6 17.7 17.7 17.6 17.6 18.5 19.6
    COPd (declared COP)   19.1 20.1 19.3 23.8 17.8 17.7 18.3 16.7 15.8 16.0 17.0 19.4 19.4 19.3 19.3 18.8 18.9
  B Condition (2°C) COPd (declared COP)   13.0 11.4 10.7 9.5 11.4 12.1 11.4 10.7 10.0 9.5 11.0 11.4 11.1 10.9 10.7 10.2 9.8
    Pdh (declared heating cap) kW 13.5 17.0 20.2 24.3 26.9 30.4 33.9 40.4 44.4 48.5 37.2 50.9 54.1 57.3 60.6 64.6 68.6
  C Condition (7°C) COPd (declared COP)   19.1 16.8 15.5 14.3 16.3 17.8 16.8 15.5 14.8 14.3 16.1 16.8 16.3 15.9 15.5 15.0 14.6
    Pdh (declared heating cap) kW 8.9 10.9 13.0 15.8 17.5 19.8 21.8 26.0 28.6 31.2 23.9 32.7 34.8 36.9 38.9 41.5 44.1
  A Condition (-7°C) COPd (declared COP)   8.1 7.1 6.6 5.8 6.9 7.5 7.1 6.6 6.1 5.7 6.8 7.1 6.9 6.7 6.6 6.3 6.0
    Pdh (declared heating cap) kW 22.1 27.9 33.2 39.6 44.2 50.0 55.7 66.3 73.0 79.6 61.0 83.6 88.9 94.2 99.5 106.2 112.8
  TBivalent Pdh (declared heating cap) kW 25.0 31.5 37.5 45.0 50.0 56.5 63.0 75.0 82.5 90.0 69.0 94.5 100.5 106.5 112.5 120.0 127.5
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)   7.2 6.1 5.8 5.8 6.1 6.6 6.2 5.8 5.3 4.9 6.0 6.2 6.1 5.9 5.8 5.4 5.1
Piping connections HP/LP gas OD mm 15.9 (12), 19.1 (13) 19.1 (12), 22.2 (13) 19.1 (12), 28.6 (13) 22.2 (12), 28.6 (13) 22.2 (12), 28.6 (13) 22.2 (12), 28.6 (13) 28.6 (12), 28.6 (13) 28.6 (12), 34.9 (13) 28.6 (12), 34.9 (13) 28.6 (12), 34.9 (13) 28.6 (12), 28.6 (13) 28.6 (12), 34.9 (13) 28.6 (12), 34.9 (13) 28.6 (12), 34.9 (13) 28.6 (12), 41.3 (13) 41.3 (13), 34.9 (12) 41.3 (13), 34.9 (12)
  Liquid OD mm 9.52 9.52 12.70 12.70 12.70 15.90 15.90 15.90 19.10 19.10 15.90 19.10 19.10 19.10 19.10 19.10 19.10
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Total piping length System Actual m 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14) 500 (14)
  Gas OD mm 19.1 (11) 22.2 (11) 28.6 (11) 28.6 (11) 28.6 (11) 28.6 (11) 28.6 (11) 34.9 (11) 34.9 (11) 34.9 (11) 28.6 (11) 34.9 (11) 34.9 (11) 34.9 (11) 41.3 (11) 41.3 (11) 41.3 (11)
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
SEER 8.4 7.9 9.2 8.5 7.9 7.9 7.7 8.8 8.3 7.9 8.0 7.9 8.2 8.8 9.0 8.7 8.7 8.5
Sound power level Cooling Nom. dBA 65.0 (9) 71.0 (9) 72.0 (9) 74.0 (9) 68.0 (9) 72.0 (9) 74.0 (9) 75.0 (9) 76.0 (9) 77.0 (9) 75.0 (9) 76.0 (9) 76.0 (9) 76.0 (9) 77.0 (9) 78.0 (9) 78.0 (9)
Dimensions Unit Width mm 767 767 767 767
    Depth mm 560 560 560 560
    Height mm 980 980 980 980
ηs,h % 524.3 465.9 436.0 397.1 459.2 491.1 466.8 434.5 406.9 387.9 447.9 467.2 456.1 447.0 438.5 419.4 404.4
Heating capacity Prated,h kW 25.0 31.5 37.5 45.0 50.0 56.5 62.5 75.0 82.5 90.0 69.0 94.5 100.5 106.5 112.5 120.0 127.5
Power supply Phase   3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
  Name   Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m.
  (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998
  (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 (3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998
  (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010
  (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 (5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010
  (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m
  (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
  (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. (8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2.
  (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates. (9) - Sound power level is an absolute value that a sound source generates.
  (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used (11) - In case of heat pump system, gas pipe is not used
  (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system (12) - In case of heat recovery system
  (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system (13) - In case of heat pump system
  (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual (14) - Refer to refrigerant pipe selection or installation manual
  (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C
  (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (16) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set. (20) - TOCA means the total value of each OC set.
  (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%. (21) - Maximum allowable voltage range variation between phases is 2%.
  (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room. (23) - Sound values are measured in a semi-anechoic room.
  (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
  (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
  (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power (26) - Ssc: Short-circuit power
  (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual (27) - For detailed contents of standard accessories, see installation/operation manual
  (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination (28) - Multi combination (10~54HP) data is corresponding with the standard multi combination
Piping connections Drain Type                                     Flexible PVC hose
System Outdoor unit module 1                                     RWEYQ14T
  Outdoor unit module 2                                     RWEYQ14T
  Outdoor unit module 3                                     RWEYQ14T
Cooling capacity Prated,c kW                                   120
Heating capacity Prated,h kW                                   135
Space cooling A Condition (35°C - 27/19), cooling tower (inlet/outlet) 30/35 EERd %                                   4.5
    Pdc kW                                   120.0
  B Condition (30°C - 27/19), cooling tower (inlet/outlet) 26/* EERd %                                   6.3
    Pdc kW                                   88.4
  C Condition (25°C - 27/19), cooling tower (inlet/outlet) 22/* EERd %                                   9.4
    Pdc kW                                   56.8
  D Condition (20°C - 27/19), cooling tower (inlet/outlet) 18/* EERd %                                   15.4
    Pdc kW                                   25.3
Space heating (Average climate) TBivalent COPd (declared COP)                                     4.9
    Pdh (declared heating cap) kW                                   135.0
    Tbiv (bivalent temperature) °C                                   -10
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)                                     4.9
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW                                   135.0
  TOL Tol (temperature operating limit) °C                                   -10
  A Condition (-7°C) COPd (declared COP)                                     5.7
    Pdh (declared heating cap) kW                                   119.4
  B Condition (2°C) COPd (declared COP)                                     9.5
    Pdh (declared heating cap) kW                                   72.7
  C Condition (7°C) COPd (declared COP)                                     14.3
    Pdh (declared heating cap) kW                                   46.7
  D Condition (12°C) COPd (declared COP)                                     18.4
    Pdh (declared heating cap) kW                                   20.8
Indoor index connection Min.                                     525
  Max.                                     1575
Sound power level Cooling Nom. dBA                                   79.0 (9)
Sound pressure level Cooling Nom. dBA                                   63
Refrigerant Type                                     R-410A
  GWP                                     2087.5
Piping connections Liquid Type                                     Braze connection
    OD mm                                   19.1
  Gas Type                                     Braze connection
    OD mm                                   41.3 (11)
  HP/LP gas OD mm                                   41.3 (13), 34.9 (12)
  Total piping length System Actual m                                   500 (14)
Power supply Name                                     Y1
  Phase                                     3N~
  Frequency Hz                                   50
  Voltage V                                   380-415