Specifications Table for RXF-D9

RXF60D5V1B9 RXF71D5V1B9
Dimensions Unit Height mm 734 734
    Width mm 870 870
    Depth mm 373 373
Weight Unit kg 50 50
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor
Operation range Cooling Ambient Min. °CDB -10 -10
      Max. °CDB 48 48
  Heating Ambient Min. °CWB -15 -15
      Max. °CWB 18 18
Sound pressure level Cooling Nom. dBA 49 52
  Heating Nom. dBA 49 52
Refrigerant Type   R-32 R-32
  Charge kg 1.15 1.15
  Charge tCO2Eq 0.78 0.78
  GWP   675 675
Piping connections Piping length OU - IU Max. m 30 30
  Additional refrigerant charge kg/m 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m)
  Level difference IU - OU Max. m 20 20
Standard Accessories Installation manual 1 1
  Refrigerant charge label 1 1
  Multilingual fluorinated greenhouse gases labels 1 1
  Drain cap 3 3
  Drain plug 1 1
Power supply Phase   1~ 1~
  Frequency Hz 50 50
  Voltage V 220-240 220-240
Notes (1) - See separate drawing for operation range (1) - See separate drawing for operation range
  (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data
  (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases