| RXYCQ8A7Y1B | RXYCQ10A7Y1B | RXYCQ12A7Y1B | RXYCQ14A7Y1B | RXYCQ16A7Y1B | RXYCQ18A7Y1B | RXYCQ20A7Y1B | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Cooling | Nom. | dBA | 58 | 59 | 61 | 61 | 64 | 65 | 66 | |
| Standard Accessories | Installation manual | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||
| Operation manual | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Connection pipes | 4 | 4 | 4 | 4 | 4 | 4 | 4 | ||||
| Capacity range | HP | 8 | 10 | 12 | 14 | 16 | 18 | 20 | |||
| Operation range | Cooling | Max. | °CDB | 43 | 43 | 43 | 43 | 43 | 43 | 43 | |
| Min. | °CDB | -5 | -5 | -5 | -5 | -5 | -5 | -5 | |||
| Heating | Min. | °CWB | -20 | -20 | -20 | -20 | -20 | -20 | -20 | ||
| Max. | °CWB | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | |||
| Maximum number of connectable indoor units | 64 | 64 | 64 | 64 | 64 | 64 | 64 | ||||
| Compressor | Type | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | |||
| Weight | Unit | kg | 159 | 187 | 240 | 240 | 316 | 316 | 324 | ||
| Refrigerant | Charge | TCO2Eq | 12.9 | 16.1 | 17.5 | 18 | 23.6 | 24 | 24.4 | ||
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | ||||
| Charge | kg | 6.2 | 7.7 | 8.4 | 8.6 | 11.3 | 11.5 | 11.7 | |||
| Type | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | ||||
| Indoor index connection | Nom. | 200 | 250 | 300 | 350 | 400 | 450 | 500 | |||
| Min. | 100 | 125 | 150 | 175 | 200 | 225 | 250 | ||||
| Max. | 200 | 250 | 360 | 420 | 480 | 540 | 600 | ||||
| Piping connections | Liquid | OD | mm | 9.52 | 9.52 | 9.52 | 12.7 | 12.7 | 12.7 | 15.9 | |
| Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | ||||
| Total piping length | System | Actual | m | 300 | 300 | 300 | 300 | 300 | 300 | 300 | |
| Gas | OD | mm | 15.9 | 19.1 | 22.2 | 28.6 | 28.6 | 28.6 | 28.6 | ||
| Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | ||||
| Level difference | OU - IU | Outdoor unit in highest position | m | 30 | 30 | 30 | 30 | 30 | 30 | 30 | |
| IU - IU | Max. | m | 15 | 15 | 15 | 15 | 15 | 15 | 15 | ||
| Heat insulation | Both liquid and gas pipes | Both liquid and gas pipes | Both liquid and gas pipes | Both liquid and gas pipes | Both liquid and gas pipes | Both liquid and gas pipes | Both liquid and gas pipes | ||||
| Sound power level | Cooling | Nom. | dBA | 78 | 81 | 81 | 81 | 86 | 86 | 88 | |
| Dimensions | Unit | Width | mm | 635 | 930 | 930 | 930 | 1,240 | 1,240 | 1,240 | |
| Depth | mm | 765 | 765 | 765 | 765 | 765 | 765 | 765 | |||
| Height | mm | 1,680 | 1,680 | 1,680 | 1,680 | 1,680 | 1,680 | 1,680 | |||
| Fan | External static pressure | Max. | Pa | 78 | 78 | 78 | 78 | 78 | 78 | 78 | |
| Power supply | Phase | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | |||
| Name | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | ||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||
| Voltage | V | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. | |||||
| (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | |||||
| (4) - The maximum capacities for RXYCQ8A7Y1B and RXYCQ10A7Y1B can be up to 240 and 300 respectively if no FXFQ20/25 indoor units are present in the setup. | (4) - The maximum capacities for RXYCQ8A7Y1B and RXYCQ10A7Y1B can be up to 240 and 300 respectively if no FXFQ20/25 indoor units are present in the setup. | (4) - The maximum capacities for RXYCQ8A7Y1B and RXYCQ10A7Y1B can be up to 240 and 300 respectively if no FXFQ20/25 indoor units are present in the setup. | (4) - The maximum capacities for RXYCQ8A7Y1B and RXYCQ10A7Y1B can be up to 240 and 300 respectively if no FXFQ20/25 indoor units are present in the setup. | (4) - The maximum capacities for RXYCQ8A7Y1B and RXYCQ10A7Y1B can be up to 240 and 300 respectively if no FXFQ20/25 indoor units are present in the setup. | (4) - The maximum capacities for RXYCQ8A7Y1B and RXYCQ10A7Y1B can be up to 240 and 300 respectively if no FXFQ20/25 indoor units are present in the setup. | (4) - The maximum capacities for RXYCQ8A7Y1B and RXYCQ10A7Y1B can be up to 240 and 300 respectively if no FXFQ20/25 indoor units are present in the setup. | |||||
| (5) - Sound power level is an absolute value that a sound source generates. | (5) - Sound power level is an absolute value that a sound source generates. | (5) - Sound power level is an absolute value that a sound source generates. | (5) - Sound power level is an absolute value that a sound source generates. | (5) - Sound power level is an absolute value that a sound source generates. | (5) - Sound power level is an absolute value that a sound source generates. | (5) - Sound power level is an absolute value that a sound source generates. | |||||
| (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||
| (7) - Sound values are measured in a semi-anechoic room. | (7) - Sound values are measured in a semi-anechoic room. | (7) - Sound values are measured in a semi-anechoic room. | (7) - Sound values are measured in a semi-anechoic room. | (7) - Sound values are measured in a semi-anechoic room. | (7) - Sound values are measured in a semi-anechoic room. | (7) - Sound values are measured in a semi-anechoic room. | |||||
| (8) - Refer to refrigerant pipe selection or installation manual | (8) - Refer to refrigerant pipe selection or installation manual | (8) - Refer to refrigerant pipe selection or installation manual | (8) - Refer to refrigerant pipe selection or installation manual | (8) - Refer to refrigerant pipe selection or installation manual | (8) - Refer to refrigerant pipe selection or installation manual | (8) - Refer to refrigerant pipe selection or installation manual | |||||
| (9) - For detailed contents of standard accessories see Installation manual. | (9) - For detailed contents of standard accessories see Installation manual. | (9) - For detailed contents of standard accessories see Installation manual. | (9) - For detailed contents of standard accessories see Installation manual. | (9) - For detailed contents of standard accessories see Installation manual. | (9) - For detailed contents of standard accessories see Installation manual. | (9) - For detailed contents of standard accessories see Installation manual. | |||||
| (10) - RLA is based on nominal conditions | (10) - RLA is based on nominal conditions | (10) - RLA is based on nominal conditions | (10) - RLA is based on nominal conditions | (10) - RLA is based on nominal conditions | (10) - RLA is based on nominal conditions | (10) - RLA is based on nominal conditions | |||||
| (11) - MSC means the maximum current during start up of the compressor | (11) - MSC means the maximum current during start up of the compressor | (11) - MSC means the maximum current during start up of the compressor | (11) - MSC means the maximum current during start up of the compressor | (11) - MSC means the maximum current during start up of the compressor | (11) - MSC means the maximum current during start up of the compressor | (11) - MSC means the maximum current during start up of the compressor | |||||
| (12) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (12) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (12) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (12) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (12) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (12) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (12) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||
| (13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||
| (14) - TOCA means the total value of each OC set. | (14) - TOCA means the total value of each OC set. | (14) - TOCA means the total value of each OC set. | (14) - TOCA means the total value of each OC set. | (14) - TOCA means the total value of each OC set. | (14) - TOCA means the total value of each OC set. | (14) - TOCA means the total value of each OC set. | |||||
| (15) - FLA means the nominal running current of the fan | (15) - FLA means the nominal running current of the fan | (15) - FLA means the nominal running current of the fan | (15) - FLA means the nominal running current of the fan | (15) - FLA means the nominal running current of the fan | (15) - FLA means the nominal running current of the fan | (15) - FLA means the nominal running current of the fan | |||||
| (16) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (16) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (16) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (16) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (16) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (16) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (16) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (18) - Contains fluorinated greenhouse gases | (18) - Contains fluorinated greenhouse gases | (18) - Contains fluorinated greenhouse gases | (18) - Contains fluorinated greenhouse gases | (18) - Contains fluorinated greenhouse gases | (18) - Contains fluorinated greenhouse gases | (18) - Contains fluorinated greenhouse gases | |||||
| (19) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. | (19) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. | (19) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. | (19) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. | (19) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. | (19) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. | (19) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. | |||||
| (20) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A | (20) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A | (20) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A | (20) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A | (20) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A | (20) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A | (20) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A | |||||
| (21) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (21) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (21) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (21) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (21) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (21) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (21) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | |||||
| (22) - Short-circuit power | (22) - Short-circuit power | (22) - Short-circuit power | (22) - Short-circuit power | (22) - Short-circuit power | (22) - Short-circuit power | (22) - Short-circuit power | |||||
| (23) - system impedance | (23) - system impedance | (23) - system impedance | (23) - system impedance | (23) - system impedance | (23) - system impedance | (23) - system impedance | |||||
| (24) - For RXYCQ8 and RXYCQ10 MSC ≤ MCA | (24) - For RXYCQ8 and RXYCQ10 MSC ≤ MCA | (24) - For RXYCQ8 and RXYCQ10 MSC ≤ MCA | (24) - For RXYCQ8 and RXYCQ10 MSC ≤ MCA | (24) - For RXYCQ8 and RXYCQ10 MSC ≤ MCA | (24) - For RXYCQ8 and RXYCQ10 MSC ≤ MCA | (24) - For RXYCQ8 and RXYCQ10 MSC ≤ MCA | |||||