Specifications Table for RXYN-B

RXYN10B7Y1B
Recommended combination 4 x FXSN63B2VEB
Recommended combination 2 4 x FXFN63B2VEB
Cooling capacity Prated,c kW 28.0 (1)
Heating capacity Prated,h kW 28.0 (2)
  Nom. 6°CWB kW 28.00 (2)
COP at nom. capacity 6°CWB KW/KW 294.00 (2)
SEER 4.80
SEER recommended combination 2 4.80
SCOP 3.50
SCOP recommended combination 2 3.50
Space cooling A Condition (35°C - 27/19) EERd   1.88
    Pdc kW 28.0
  B Condition (30°C - 27/19) EERd   2.88
    Pdc kW 20.6
  C Condition (25°C - 27/19) EERd   6.40
    Pdc kW 13.3
  D Condition (20°C - 27/19) EERd   12.3
    Pdc kW 8.28
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd   1.88
    Pdc kW 28.0
  B Condition (30°C - 27/19) EERd   2.88
    Pdc kW 20.6
  C Condition (25°C - 27/19) EERd   6.40
    Pdc kW 13.3
  D Condition (20°C - 27/19) EERd   12.3
    Pdc kW 8.28
Space heating (Average climate) TBivalent COPd (declared COP)   1.53
    Pdh (declared heating cap) kW 16.0
    Tbiv (bivalent temperature) °C -10.0
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)   1.53
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW 16.0
  TOL Tol (temperature operating limit) °C -10
  A Condition (-7°C) COPd (declared COP)   2.14
    Pdh (declared heating cap) kW 14.2
  B Condition (2°C) COPd (declared COP)   3.34
    Pdh (declared heating cap) kW 8.62
  C Condition (7°C) COPd (declared COP)   5.00
    Pdh (declared heating cap) kW 5.54
  D Condition (12°C) COPd (declared COP)   6.52
    Pdh (declared heating cap) kW 7.04
Space heating (Average climate) recommended combination 2 TBivalent COPd (declared COP)   1.53
    Pdh (declared heating cap) kW 16.0
    Tbiv (bivalent temperature) °C -10.0
  TOL COPd (declared COP)   1.53
    Pdh (declared heating cap) kW 16.0
    Tol (temperature operating limit) °C -10
  A Condition (-7°C) COPd (declared COP)   2.14
    Pdh (declared heating cap) kW 14.2
  B Condition (2°C) COPd (declared COP)   3.34
    Pdh (declared heating cap) kW 8.62
  C Condition (7°C) COPd (declared COP)   5.00
    Pdh (declared heating cap) kW 5.54
  D Condition (12°C) COPd (declared COP)   6.52
    Pdh (declared heating cap) kW 7.04
Capacity range HP 10
Maximum number of connectable indoor units 8 (3)
Indoor index connection Min.   125
  Max.   325
Dimensions Unit Height mm 1,680
    Width mm 1930
    Depth mm 765
Weight Unit kg 564
Compressor Type   Hermetically sealed swing compressor
Operation range Cooling Min. °CDB -5
    Max. °CDB 43
  Heating Min. °CWB -20
    Max. °CWB 16
Sound power level Cooling Nom. dBA 835.0 (4)
Sound pressure level Cooling Nom. dBA 608.0 (5)
Refrigerant Type   R744 (CO2)
  GWP   1.0
  Charge tCO2Eq 0.00
  Charge kg 0.00
Piping connections Liquid Type   Braze connection
    OD mm 9.52
  Gas Type   Braze connection
    OD mm 15.9
  Total piping length System Actual m 300 (6)
Standard Accessories Installation manual 1
  Auxiliary piping set 1
  General safety precautions 1
  Operation manual 1
  Safety valve 2
  Changeover valve 1
  Declaration of conformity 1
Power supply Name   Y1
  Phase   3N~
  Frequency Hz 50
  Voltage V 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system.
  (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (12) - Maximum allowable voltage range variation between phases is 2%.
  (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (14) - Sound values are measured in a semi-anechoic room.
  (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
  (16) - Ssc: Short-circuit power
  (17) - For detailed contents of standard accessories, see installation/operation manual