| RXYSQ4T7Y1B | RXYSQ5T7Y1B | RXYSQ6T7Y1B | RXYSQ8TMY1B | RXYSQ10TMY1B | RXYSQ12TMY1B | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Cooling | Nom. | dBA | 50 (5) | 51 (5) | 55.0 (8) | 55.0 (8) | 57.0 (8) | ||
| Standard Accessories | Installation manual | Installation manual | Installation manual | Installation manual | 1 | 1 | 1 | |||
| Operation manual | Operation manual | Operation manual | Operation manual | 1 | 1 | 1 | ||||
| Connection pipes | Connection pipes | Connection pipes | Connection pipes | 1 | 1 | 1 | ||||
| SEER recommended combination 2 | 6.0 | 6.3 | 6.3 | |||||||
| Capacity range | HP | 4 | 5 | 6 | 8 | 10 | 12 | |||
| Operation range | Cooling | Max. | °CDB | 46 | 46 | 52.0 | 52.0 | 52.0 | ||
| Min. | °CDB | -5 | -5 | -5.0 | -5.0 | -5.0 | ||||
| Heating | Min. | °CWB | -20 | -20 | -20.0 | -20.0 | -20.0 | |||
| Max. | °CWB | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | ||||
| Maximum number of connectable indoor units | 64 (3) | 64 (3) | 64 (3) | 64 (6) | 64 (6) | 64 (6) | ||||
| Space cooling | B Condition (30°C - 27/19) | Pdc | kW | 16.5 | 20.6 | 24.7 | ||||
| EERd | 4.2 | 4.3 | 4.3 | |||||||
| D Condition (20°C - 27/19) | Pdc | kW | 6.4 | 7.1 | 7.3 | |||||
| EERd | 13.7 | 12.2 | 13.6 | |||||||
| A Condition (35°C - 27/19) | EERd | 2.6 | 2.8 | 2.7 | ||||||
| Pdc | kW | 22.4 | 28.0 | 33.5 | ||||||
| C Condition (25°C - 27/19) | EERd | 7.7 | 7.7 | 7.9 | ||||||
| Pdc | kW | 10.6 | 13.3 | 15.9 | ||||||
| SCOP | 4.2 | 4.1 | 4.3 | |||||||
| Compressor | Type | Hermetically sealed swing compressor | Hermetically sealed swing compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | ||||
| Weight | Unit | kg | 104 | 104 | 144 | 175 | 180 | |||
| Refrigerant | Charge | TCO2Eq | 7.5 | 7.5 | ||||||
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | |||||
| Charge | kg | 3.6 | 3.6 | 5.5 | 7.0 | 8.0 | ||||
| Type | R-410A | R-410A | R-410A | R-410A | R-410A | |||||
| Space cooling recommended combination 2 | C Condition (25°C - 27/19) | Pdc | kW | 10.6 | 13.3 | 15.9 | ||||
| EERd | 7.5 | 7.7 | 7.7 | |||||||
| A Condition (35°C - 27/19) | EERd | 2.3 | 2.8 | 2.5 | ||||||
| Pdc | kW | 22.4 | 28.0 | 33.5 | ||||||
| D Condition (20°C - 27/19) | EERd | 13.4 | 12.4 | 13.5 | ||||||
| Pdc | kW | 6.4 | 7.3 | 7.3 | ||||||
| B Condition (30°C - 27/19) | EERd | 4.2 | 4.4 | 4.2 | ||||||
| Pdc | kW | 16.5 | 20.6 | 24.7 | ||||||
| Recommended combination 2 | 4 x FXSQ50A2VEB | 4 x FXSQ63A2VEB | 6 x FXSQ50A2VEB | |||||||
| SCOP recommended combination 2 | 4.2 | 4.1 | 4.3 | |||||||
| Power input - 50Hz | Cooling | Nom. | Eurovent | kW | 3.03 (1) | 3.73 (1) | ||||
| Heating | Nom. | 6°CWB | kW | 2.68 (2) | 3.27 (2) | 5.82 (5) | 6.60 (5) | 8.19 (5) | ||
| Indoor index connection | Min. | 50 | 62.5 | 100.0 | 125.0 | 150.0 | ||||
| Max. | 130 | 162.5 | 260.0 | 325.0 | 390.0 | |||||
| Cooling capacity | Nom. | Eurovent | kW | 12.1 (1) | 14.0 (1) | |||||
| COP at nom. capacity | 6°CWB | kW/kW | 4.52 (2) | 4.28 (2) | 3.85 | 4.24 | 4.09 | |||
| Recommended combination | 4 x FXMQ50P7VEB | 4 x FXMQ63P7VEB | 6 x FXMQ50P7VEB | |||||||
| Space heating (Average climate) | TOL | COPd (declared COP) | 2.4 | 2.2 | 2.2 | |||||
| Pdh (declared heating cap) | kW | 14.9 | 19.6 | 23.5 | ||||||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | ||||||
| D Condition (12°C) | Pdh (declared heating cap) | kW | 5.8 | 6.4 | 6.6 | |||||
| COPd (declared COP) | 7.8 | 6.3 | 6.7 | |||||||
| B Condition (2°C) | COPd (declared COP) | 4.0 | 4.1 | 4.3 | ||||||
| Pdh (declared heating cap) | kW | 8.0 | 10.6 | 12.7 | ||||||
| C Condition (7°C) | COPd (declared COP) | 5.9 | 5.9 | 6.3 | ||||||
| Pdh (declared heating cap) | kW | 5.0 | 6.8 | 8.1 | ||||||
| A Condition (-7°C) | COPd (declared COP) | 2.6 | 2.4 | 2.4 | ||||||
| Pdh (declared heating cap) | kW | 13.2 | 17.4 | 20.8 | ||||||
| TBivalent | Pdh (declared heating cap) | kW | 14.9 | 19.6 | 23.5 | |||||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | ||||||
| COPd (declared COP) | 2.4 | 2.2 | 2.2 | |||||||
| Piping connections | Liquid | OD | mm | 9.52 | 9.52 | 9.52 | 9.52 | 12.7 | ||
| Type | Flare connection | Flare connection | Braze connection | Braze connection | Braze connection | |||||
| Total piping length | System | Actual | m | 300 (9) | 300 (9) | 300 (9) | ||||
| Gas | OD | mm | 15.9 | 15.9 | 19.1 | 22.2 | 25.4 | |||
| Type | Flare connection | Flare connection | Braze connection | Braze connection | Braze connection | |||||
| Heat insulation | Both liquid and gas pipes | Both liquid and gas pipes | ||||||||
| SEER | 6.3 | 6.3 | 6.5 | |||||||
| Space heating (Average climate) recommended combination 2 | B Condition (2°C) | Pdh (declared heating cap) | kW | 8.0 | 10.6 | 12.7 | ||||
| COPd (declared COP) | 4.0 | 4.1 | 4.2 | |||||||
| C Condition (7°C) | Pdh (declared heating cap) | kW | 5.2 | 6.8 | 8.1 | |||||
| COPd (declared COP) | 5.8 | 5.9 | 6.2 | |||||||
| A Condition (-7°C) | COPd (declared COP) | 2.6 | 2.4 | 2.3 | ||||||
| Pdh (declared heating cap) | kW | 13.2 | 17.4 | 20.8 | ||||||
| D Condition (12°C) | Pdh (declared heating cap) | kW | 5.7 | 6.4 | 6.5 | |||||
| COPd (declared COP) | 7.7 | 6.3 | 6.6 | |||||||
| TBivalent | Pdh (declared heating cap) | kW | 14.9 | 19.6 | 23.5 | |||||
| COPd (declared COP) | 2.3 | 2.2 | 2.2 | |||||||
| Tbiv (bivalent temperature) | °C | -10.0 | -10.0 | -10.0 | ||||||
| Sound power level | Cooling | Nom. | dBA | 68 (4) | 69 (4) | 73.0 (7) | 74.0 (7) | 76.0 (7) | ||
| Dimensions | Unit | Width | mm | 900 | 900 | 940 | 940 | 940 | ||
| Depth | mm | 320 | 320 | 320 | 460 | 460 | ||||
| Height | mm | 1,345 | 1,345 | 1,430 | 1,615 | 1,615 | ||||
| Fan | Air flow rate | Cooling | Nom. | m³/min | 106 | 106 | ||||
| Heating capacity | Nom. | 6°CWB | kW | 12.1 (2) | 14.0 (2) | 22.4 (5) | 28.0 (5) | 33.5 (5) | ||
| Power supply | Phase | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | ||||
| Name | Y1 | Y1 | Y1 | Y1 | Y1 | |||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | ||||
| Voltage | V | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | ||||
| Notes | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series. Eurovent 2015 tolerances are used. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series. Eurovent 2015 tolerances are used. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series. Eurovent 2015 tolerances are used. | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||
| (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series. Eurovent 2015 tolerances are used. | (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series. Eurovent 2015 tolerances are used. | (2) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | (2) - Cooling: T1: indoor temp. 26,7°CDB, 19,4°CWB, outdoor temp. 35°CB, AHRI 1230:2010, power input indoor units (duct type) included | (2) - Cooling: T1: indoor temp. 26,7°CDB, 19,4°CWB, outdoor temp. 35°CB, AHRI 1230:2010, power input indoor units (duct type) included | (2) - Cooling: T1: indoor temp. 26,7°CDB, 19,4°CWB, outdoor temp. 35°CB, AHRI 1230:2010, power input indoor units (duct type) included | |||||
| (3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | (3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | (3) - Sound power level is an absolute value that a sound source generates. | (3) - Cooling: T3: indoor temp. 29,0°CDB, 19,0°CWB, outdoor temp. 46°CB, ISO15042:2011, power input indoor units (duct type) included | (3) - Cooling: T3: indoor temp. 29,0°CDB, 19,0°CWB, outdoor temp. 46°CB, ISO15042:2011, power input indoor units (duct type) included | (3) - Cooling: T3: indoor temp. 29,0°CDB, 19,0°CWB, outdoor temp. 46°CB, ISO15042:2011, power input indoor units (duct type) included | |||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (4) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CB, AHRI 1230:2010, power input indoor units (duct type) included | (4) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CB, AHRI 1230:2010, power input indoor units (duct type) included | (4) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CB, AHRI 1230:2010, power input indoor units (duct type) included | |||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (5) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (5) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (5) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||
| (6) - Sound values are measured in a semi-anechoic room. | (6) - Sound values are measured in a semi-anechoic room. | (6) - TOCA means the total value of each OC set. | (6) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | (6) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | (6) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | |||||
| (7) - For detailed contents of standard accessories, see installation/operation manual | (7) - For detailed contents of standard accessories, see installation/operation manual | (7) - Sound power level is an absolute value that a sound source generates. | (7) - Sound power level is an absolute value that a sound source generates. | (7) - Sound power level is an absolute value that a sound source generates. | ||||||
| (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (8) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (8) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (8) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | ||||||
| (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (9) - Refer to refrigerant pipe selection or installation manual | (9) - Refer to refrigerant pipe selection or installation manual | (9) - Refer to refrigerant pipe selection or installation manual | ||||||
| (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (10) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (10) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | ||||||
| (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (11) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (11) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | ||||||
| (12) - TOCA means the total value of each OC set. | (12) - TOCA means the total value of each OC set. | (12) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (12) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (12) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | ||||||
| (13) - FLA: nominal running current fan | (13) - FLA: nominal running current fan | (13) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (13) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (13) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | ||||||
| (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (14) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (14) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | ||||||
| (15) - Maximum allowable voltage range variation between phases is 2%. | (15) - Maximum allowable voltage range variation between phases is 2%. | (15) - TOCA means the total value of each OC set. | (15) - TOCA means the total value of each OC set. | (15) - TOCA means the total value of each OC set. | ||||||
| (16) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | (16) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | (16) - FLA means the nominal running current of the fan | (16) - FLA means the nominal running current of the fan | (16) - FLA means the nominal running current of the fan | ||||||
| (17) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | (17) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | (17) - Maximum allowable voltage range variation between phases is 2%. | ||||||
| Cooling capacity | Nom. | Eurovent | kW | 15.5 (1) | ||||||
| Heating capacity | Nom. | 6°CWB | kW | 15.5 (2) | ||||||
| COP at nom. capacity | 6°CWB | KW/KW | 3.9 | |||||||
| Indoor index connection | Min. | 70 | ||||||||
| Max. | 182 | |||||||||
| Dimensions | Unit | Height | mm | 1345 | ||||||
| Width | mm | 900 | ||||||||
| Depth | mm | 320 | ||||||||
| Weight | Unit | kg | 104 | |||||||
| Fan | Air flow rate | Cooling | Nom. | m³/min | 106 | |||||
| Compressor | Type | Hermetically sealed swing compressor | ||||||||
| Operation range | Cooling | Min. | °CDB | -5 | ||||||
| Max. | °CDB | 46 | ||||||||
| Heating | Min. | °CWB | -20 | |||||||
| Max. | °CWB | 15.5 | ||||||||
| Sound power level | Cooling | Nom. | dBA | 70 (4) | ||||||
| Sound pressure level | Cooling | Nom. | dBA | 51 (5) | ||||||
| Refrigerant | Type | R-410A | ||||||||
| GWP | 2087.5 | |||||||||
| Charge | tCO2Eq | 7.5 | ||||||||
| Charge | kg | 3.6 | ||||||||
| Piping connections | Liquid | OD | mm | 9.52 | ||||||
| Gas | OD | mm | 19.1 | |||||||
| Power supply | Name | Y1 | ||||||||
| Phase | 3N~ | |||||||||
| Frequency | Hz | 50 | ||||||||
| Voltage | V | 380-415 | ||||||||
| Notes | (18) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (18) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (18) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||||
| (19) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | (19) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | (19) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | ||||||||
| (20) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | (20) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | (20) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | ||||||||
| (21) - Sound values are measured in a semi-anechoic room. | (21) - Sound values are measured in a semi-anechoic room. | (21) - Sound values are measured in a semi-anechoic room. | ||||||||
| (22) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (22) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (22) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | ||||||||
| (23) - Ssc: Short-circuit power | (23) - Ssc: Short-circuit power | (23) - Ssc: Short-circuit power | ||||||||
| (24) - For detailed contents of standard accessories, see installation/operation manual | (24) - For detailed contents of standard accessories, see installation/operation manual | (24) - For detailed contents of standard accessories, see installation/operation manual | ||||||||