| RYMQ8U7Y1B | RYMQ10U7Y1B | RYMQ12U7Y1B | RYMQ14U7Y1B | RYMQ16U7Y1B | RYMQ18U7Y1B | RYMQ20U7Y1B | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Recommended combination | 4 x FXFQ50BVEB | 4 x FXFQ63BVEB | 6 x FXFQ50BVEB | 1 x FXFQ50BVEB + 5 x FXFQ63BVEB | 4 x FXFQ63BVEB + 2 x FXFQ80BVEB | 3 x FXFQ50BVEB + 5 x FXFQ63BVEB | 2 x FXFQ50BVEB + 6 x FXFQ63BVEB | ||||
| Recommended combination 2 | 4 x FXSQ50A2VEB | 4 x FXSQ63A2VEB | 6 x FXSQ50A2VEB | 1 x FXSQ50A2VEB + 5 x FXSQ63A2VEB | 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB | 2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB | ||||
| Recommended combination 3 | 4 x FXMQ50P7VEB9 | 4 x FXMQ63P7VEB9 | 6 x FXMQ50P7VEB9 | 1 x FXMQ50P7VEB9 + 5 x FXMQ63P7VEB9 | 4 x FXMQ63P7VEB9 + 2 x FXMQ80P7VEB9 | 3 x FXMQ50P7VEB9 + 5 x FXMQ63P7VEB9 | 2 x FXMQ50P7VEB9 + 6 x FXMQ63P7VEB9 | ||||
| Cooling capacity | Prated,c | kW | 22.4 (1) | 28.0 (1) | 33.5 (1) | 40.0 (1) | 45.0 (1) | 50.4 (1) | 52.0 (1) | ||
| Heating capacity | Prated,h | kW | 22.4 (2) | 28.0 (2) | 33.5 (2) | 40.0 (2) | 45.0 (2) | 50.4 (2) | 56.0 (2) | ||
| Nom. | 6°CWB | kW | 22.4 (2) | 28.0 (2) | 33.5 (2) | 40.0 (2) | 45.0 (2) | 50.4 (2) | 56.0 (2) | ||
| COP at nom. capacity | 6°CWB | KW/KW | 4.15 (2) | 3.69 (2) | 3.47 (2) | 3.74 (2) | 3.59 (2) | 3.54 (2) | 3.2 (2) | ||
| SEER | 7.6 | 6.8 | 6.3 | 6.3 | 6.0 | 6.0 | 5.9 | ||||
| SEER recommended combination 2 | 6.9 | 6.8 | 5.9 | 6.3 | 5.9 | 6.0 | 5.9 | ||||
| SEER recommended combination 3 | 7.5 | 6.8 | 6.2 | 6.2 | 5.8 | 6.0 | 5.9 | ||||
| SCOP | 4.3 | 4.3 | 4.1 | 4.0 | 4.0 | 4.2 | 4.0 | ||||
| SCOP recommended combination 2 | 4.2 | 4.3 | 4.1 | 4.0 | 4.1 | 4.2 | 4.0 | ||||
| SCOP recommended combination 3 | 4.2 | 4.1 | 4.1 | 4.0 | 4.0 | 4.1 | 3.9 | ||||
| Space cooling | A Condition (35°C - 27/19) | EERd | 3.0 | 2.3 | 2.4 | 2.6 | 2.1 | 1.9 | 1.9 | ||
| Pdc | kW | 22.4 | 28.0 | 33.5 | 40.0 | 45.0 | 50.4 | 52.0 | |||
| B Condition (30°C - 27/19) | EERd | 5.2 | 4.7 | 4.3 | 4.1 | 3.9 | 3.8 | 3.7 | |||
| Pdc | kW | 16.5 | 20.6 | 24.7 | 29.5 | 33.2 | 37.1 | 38.3 | |||
| C Condition (25°C - 27/19) | EERd | 9.5 | 8.3 | 7.7 | 7.8 | 7.7 | 7.5 | 7.3 | |||
| Pdc | kW | 10.6 | 13.3 | 15.9 | 18.9 | 21.3 | 23.9 | 24.6 | |||
| D Condition (20°C - 27/19) | EERd | 18.8 | 17.0 | 13.9 | 14.3 | 14.2 | 18.3 | 18.3 | |||
| Pdc | kW | 8.0 | 9.3 | 9.4 | 8.4 | 9.5 | 11.5 | 11.5 | |||
| Space cooling recommended combination 2 | A Condition (35°C - 27/19) | EERd | 2.6 | 2.4 | 2.4 | 2.6 | 2.1 | 1.9 | 1.9 | ||
| Pdc | kW | 22.4 | 28.0 | 33.5 | 40.0 | 45.0 | 50.4 | 52.0 | |||
| B Condition (30°C - 27/19) | EERd | 4.9 | 4.7 | 4.0 | 4.1 | 3.8 | 3.7 | 3.6 | |||
| Pdc | kW | 16.5 | 20.6 | 24.7 | 29.5 | 33.2 | 37.1 | 38.3 | |||
| C Condition (25°C - 27/19) | EERd | 8.8 | 8.5 | 7.1 | 7.9 | 7.6 | 7.5 | 7.3 | |||
| Pdc | kW | 10.6 | 13.3 | 15.9 | 18.9 | 21.3 | 23.9 | 24.6 | |||
| D Condition (20°C - 27/19) | EERd | 15.1 | 17.2 | 13.1 | 14.0 | 14.0 | 18.1 | 18.9 | |||
| Pdc | kW | 8.8 | 9.3 | 9.1 | 8.4 | 9.5 | 11.4 | 10.9 | |||
| Space cooling recommended combination 3 | A Condition (35°C - 27/19) | EERd | 3.0 | 2.3 | 2.4 | 2.6 | 2.1 | 1.9 | 1.9 | ||
| Pdc | kW | 22.4 | 28.0 | 33.5 | 40.0 | 45.0 | 50.4 | 52.0 | |||
| B Condition (30°C - 27/19) | EERd | 5.1 | 4.7 | 4.2 | 4.0 | 3.7 | 3.7 | 3.6 | |||
| Pdc | kW | 16.5 | 20.6 | 24.7 | 29.5 | 33.2 | 37.1 | 38.3 | |||
| C Condition (25°C - 27/19) | EERd | 9.6 | 8.4 | 7.7 | 7.7 | 7.4 | 7.6 | 7.3 | |||
| Pdc | kW | 10.6 | 13.3 | 15.9 | 19.0 | 21.3 | 23.9 | 24.6 | |||
| D Condition (20°C - 27/19) | EERd | 16.0 | 16.9 | 13.7 | 14.0 | 14.1 | 18.3 | 18.3 | |||
| Pdc | kW | 9.1 | 9.3 | 9.4 | 8.4 | 9.5 | 11.6 | 11.6 | |||
| Space heating (Average climate) | TBivalent | COPd (declared COP) | 2.5 | 2.4 | 2.0 | 2.3 | 2.2 | 1.9 | 1.8 | ||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 18.4 | 20.6 | 23.2 | 27.9 | 31.0 | |||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||
| Space heating (Average climate)-=-E condition (-10°C) | Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP) | 2.5 | 2.4 | 2.0 | 2.3 | 2.2 | 1.9 | 1.8 | |||
| Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW | kW | 13.7 | 16.0 | 18.4 | 20.6 | 23.2 | 27.9 | 31.0 | |||
| TOL | Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||
| A Condition (-7°C) | COPd (declared COP) | 2.7 | 2.6 | 2.4 | 2.6 | 2.6 | 2.4 | 2.1 | |||
| Pdh (declared heating cap) | kW | 12.1 | 14.2 | 16.3 | 18.2 | 20.5 | 24.7 | 27.4 | |||
| B Condition (2°C) | COPd (declared COP) | 3.9 | 3.9 | 3.9 | 3.5 | 3.5 | 3.7 | 3.6 | |||
| Pdh (declared heating cap) | kW | 7.4 | 8.6 | 9.9 | 11.1 | 12.5 | 15.0 | 16.7 | |||
| C Condition (7°C) | COPd (declared COP) | 6.3 | 6.4 | 6.1 | 6.1 | 6.3 | 6.7 | 6.5 | |||
| Pdh (declared heating cap) | kW | 5.0 | 5.5 | 6.4 | 7.1 | 8.0 | 9.7 | 10.7 | |||
| D Condition (12°C) | COPd (declared COP) | 7.9 | 8.2 | 7.9 | 8.5 | 8.6 | 9.0 | 9.1 | |||
| Pdh (declared heating cap) | kW | 5.9 | 5.9 | 6.3 | 4.9 | 4.9 | 7.1 | 7.1 | |||
| Space heating (Average climate) recommended combination 2 | TBivalent | COPd (declared COP) | 2.4 | 2.4 | 1.9 | 2.3 | 2.2 | 1.9 | 1.8 | ||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 18.4 | 20.6 | 23.2 | 27.9 | 31.0 | |||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||
| TOL | COPd (declared COP) | 2.4 | 2.4 | 1.9 | 2.3 | 2.2 | 1.9 | 1.8 | |||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 18.4 | 20.6 | 23.2 | 27.9 | 31.0 | |||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||
| A Condition (-7°C) | COPd (declared COP) | 2.7 | 2.7 | 2.4 | 2.6 | 2.6 | 2.4 | 2.2 | |||
| Pdh (declared heating cap) | kW | 12.1 | 14.2 | 16.3 | 18.2 | 20.5 | 24.7 | 27.4 | |||
| B Condition (2°C) | COPd (declared COP) | 3.9 | 4.0 | 3.9 | 3.5 | 3.5 | 3.8 | 3.7 | |||
| Pdh (declared heating cap) | kW | 7.4 | 8.6 | 9.9 | 11.1 | 12.2 | 15.0 | 16.7 | |||
| C Condition (7°C) | COPd (declared COP) | 6.3 | 6.5 | 6.1 | 6.1 | 6.3 | 6.8 | 6.5 | |||
| Pdh (declared heating cap) | kW | 5.0 | 5.5 | 6.4 | 7.1 | 8.0 | 9.7 | 10.7 | |||
| D Condition (12°C) | COPd (declared COP) | 7.8 | 8.3 | 7.9 | 8.6 | 8.7 | 9.1 | 9.2 | |||
| Pdh (declared heating cap) | kW | 5.9 | 6.0 | 6.4 | 4.9 | 5.0 | 7.2 | 7.2 | |||
| Space heating (Average climate) recommended combination 3 | TBivalent | COPd (declared COP) | 2.5 | 2.4 | 2.0 | 2.3 | 2.2 | 1.9 | 1.8 | ||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 18.4 | 20.6 | 23.2 | 27.9 | 31.0 | |||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||
| TOL | COPd (declared COP) | 2.5 | 2.4 | 2.0 | 2.3 | 2.2 | 1.9 | 1.8 | |||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 18.4 | 20.6 | 23.2 | 27.9 | 31.0 | |||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||
| A Condition (-7°C) | COPd (declared COP) | 2.7 | 2.6 | 2.4 | 2.6 | 2.6 | 2.4 | 2.1 | |||
| Pdh (declared heating cap) | kW | 12.1 | 14.2 | 16.3 | 18.2 | 20.5 | 24.7 | 27.4 | |||
| B Condition (2°C) | COPd (declared COP) | 3.9 | 3.7 | 3.9 | 3.5 | 3.5 | 3.7 | 3.6 | |||
| Pdh (declared heating cap) | kW | 7.4 | 8.6 | 9.9 | 11.1 | 12.5 | 15.0 | 16.7 | |||
| C Condition (7°C) | COPd (declared COP) | 6.2 | 6.4 | 6.0 | 6.1 | 6.2 | 6.5 | 6.3 | |||
| Pdh (declared heating cap) | kW | 4.9 | 5.5 | 6.4 | 7.1 | 8.0 | 9.7 | 10.7 | |||
| D Condition (12°C) | COPd (declared COP) | 7.8 | 8.1 | 7.8 | 8.5 | 8.6 | 8.7 | 8.7 | |||
| Pdh (declared heating cap) | kW | 5.8 | 5.9 | 6.2 | 4.9 | 4.9 | 6.9 | 6.9 | |||
| Capacity range | HP | 8 | 10 | 12 | 14 | 16 | 18 | 20 | |||
| Maximum number of connectable indoor units | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | ||||
| Indoor index connection | Min. | 100.0 | 125.0 | 150.0 | 175.0 | 200.0 | 225.0 | 250.0 | |||
| Max. | 260.0 | 325.0 | 390.0 | 455.0 | 520.0 | 585.0 | 650.0 | ||||
| Dimensions | Unit | Height | mm | 1,685 | 1,685 | 1,685 | 1,685 | 1,685 | 1,685 | 1,685 | |
| Width | mm | 930 | 930 | 930 | 1,240 | 1,240 | 1,240 | 1,240 | |||
| Depth | mm | 765 | 765 | 765 | 765 | 765 | 765 | 765 | |||
| Weight | Unit | kg | 198 | 198 | 198 | 275 | 275 | 314 | 314 | ||
| Fan | External static pressure | Max. | Pa | 78 | 78 | 78 | 78 | 78 | 78 | 78 | |
| Compressor | Type | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | |||
| Operation range | Cooling | Min. | °CDB | -5.0 | -5.0 | -5.0 | -5.0 | -5.0 | -5.0 | -5.0 | |
| Max. | °CDB | 43.0 | 43.0 | 43.0 | 43.0 | 43.0 | 43.0 | 43.0 | |||
| Heating | Min. | °CWB | -20.0 | -20.0 | -20.0 | -20.0 | -20.0 | -20.0 | -20.0 | ||
| Max. | °CWB | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | |||
| Sound power level | Cooling | Nom. | dBA | 78.0 (4) | 79.1 (4) | 83.4 (4) | 80.9 (4) | 85.6 (4) | 83.8 (4) | 87.9 (4) | |
| Sound pressure level | Cooling | Nom. | dBA | 57.0 (5) | 57.0 (5) | 61.0 (5) | 60.0 (5) | 63.0 (5) | 62.0 (5) | 65.0 (5) | |
| Refrigerant | Type | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | |||
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | ||||
| Charge | tCO2Eq | 12.3 | 12.5 | 13.2 | 21.5 | 23.6 | 24.4 | 24.6 | |||
| Charge | kg | 5.9 | 6.0 | 6.3 | 10.3 | 11.3 | 11.7 | 11.8 | |||
| Piping connections | Liquid | Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | ||
| OD | mm | 9.52 | 9.52 | 12.7 | 12.7 | 12.7 | 15.9 | 15.9 | |||
| Gas | Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | |||
| OD | mm | 19.1 | 22.2 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | |||
| Equalizing | OD | mm | 19.1 | 22.2 | 22.2 | 22.2 | 22.2 | 28.6 | 28.6 | ||
| Total piping length | System | Actual | m | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | |
| Standard Accessories | Installation manual | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||
| Operation manual | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Connection pipes | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Power supply | Name | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | |||
| Phase | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | ||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||
| Voltage | V | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||
| (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | |||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | |||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||
| (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | |||||
| (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | |||||
| (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | |||||
| (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||
| (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||
| (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | |||||
| (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | |||||
| (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | |||||
| (16) - Sound values are measured in a semi-anechoic room. | (16) - Sound values are measured in a semi-anechoic room. | (16) - Sound values are measured in a semi-anechoic room. | (16) - Sound values are measured in a semi-anechoic room. | (16) - Sound values are measured in a semi-anechoic room. | (16) - Sound values are measured in a semi-anechoic room. | (16) - Sound values are measured in a semi-anechoic room. | |||||
| (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | |||||
| (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | |||||
| (19) - Ssc: Short-circuit power | (19) - Ssc: Short-circuit power | (19) - Ssc: Short-circuit power | (19) - Ssc: Short-circuit power | (19) - Ssc: Short-circuit power | (19) - Ssc: Short-circuit power | (19) - Ssc: Short-circuit power | |||||
| (20) - For detailed contents of standard accessories, see installation/operation manual | (20) - For detailed contents of standard accessories, see installation/operation manual | (20) - For detailed contents of standard accessories, see installation/operation manual | (20) - For detailed contents of standard accessories, see installation/operation manual | (20) - For detailed contents of standard accessories, see installation/operation manual | (20) - For detailed contents of standard accessories, see installation/operation manual | (20) - For detailed contents of standard accessories, see installation/operation manual | |||||
| (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination | |||||