|
SB.RKXYQ8T7Y1B |
SB.RKXYQ8T |
SB.RKXYQ5T (Archived) |
Refrigerant
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
Notes
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
|
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%).
|
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%).
|
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%).
|
|
(4) - Sound power level is an absolute value that a sound source generates.
|
(4) - Sound power level is an absolute value that a sound source generates.
|
(4) - Sound power level is an absolute value that a sound source generates.
|
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
|
(6) - Refer to refrigerant pipe selection or installation manual
|
(6) - Refer to refrigerant pipe selection or installation manual
|
(6) - Refer to refrigerant pipe selection or installation manual
|
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
|
(12) - TOCA means the total value of each OC set.
|
(12) - TOCA means the total value of each OC set.
|
(12) - TOCA means the total value of each OC set.
|
|
(13) - FLA means the nominal running current of the fan
|
(13) - FLA means the nominal running current of the fan
|
(13) - FLA means the nominal running current of the fan
|
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
|
(16) - Sound values are measured in a semi-anechoic room.
|
(16) - Sound values are measured in a semi-anechoic room.
|
(16) - Sound values are measured in a semi-anechoic room.
|
|
(17) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(17) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(17) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
|
(18) - Ssc: Short-circuit power
|
(18) - Ssc: Short-circuit power
|
(18) - Ssc: Short-circuit power
|
|
(19) - For detailed contents of standard accessories, see installation/operation manual
|
(19) - For detailed contents of standard accessories, see installation/operation manual
|
(19) - For detailed contents of standard accessories, see installation/operation manual
|
SEER recommended combination 2
|
|
4.8
|
Capacity range
|
HP
|
|
8
|
5
|
Operation range
|
Cooling
|
Max.
|
°CDB
|
|
46.0
|
46.0
|
|
|
Min.
|
°CDB
|
|
-5.0
|
-5.0
|
|
Heating
|
Min.
|
°CWB
|
|
-20.0
|
-20.0
|
|
|
Max.
|
°CWB
|
|
15.5
|
15.5
|
ηs,c
|
%
|
|
191.1
|
Maximum number of connectable indoor units
|
|
17 (3)
|
10 (3)
|
Space cooling
|
B Condition (30°C - 27/19)
|
Pdc
|
kW
|
|
16.5
|
10.3
|
|
|
EERd
|
|
|
3.7
|
4.0
|
|
D Condition (20°C - 27/19)
|
Pdc
|
kW
|
|
6.4
|
4.8
|
|
|
EERd
|
|
|
10.5
|
9.4
|
|
A Condition (35°C - 27/19)
|
EERd
|
|
|
2.2
|
2.4
|
|
|
Pdc
|
kW
|
|
22.4
|
14.0
|
|
C Condition (25°C - 27/19)
|
EERd
|
|
|
5.5
|
6.5
|
|
|
Pdc
|
kW
|
|
10.6
|
6.6
|
SCOP
|
|
3.6
|
3.8
|
Refrigerant
|
GWP
|
|
|
2,087.5
|
Space cooling recommended combination 2
|
C Condition (25°C - 27/19)
|
Pdc
|
kW
|
|
10.6
|
|
|
EERd
|
|
|
5.6
|
|
A Condition (35°C - 27/19)
|
EERd
|
|
|
2.1
|
|
|
Pdc
|
kW
|
|
22.4
|
|
D Condition (20°C - 27/19)
|
EERd
|
|
|
10.7
|
|
|
Pdc
|
kW
|
|
6.4
|
|
B Condition (30°C - 27/19)
|
EERd
|
|
|
3.7
|
|
|
Pdc
|
kW
|
|
16.5
|
System
|
Compressor unit
|
|
|
RKXYQ8T
|
RKXYQ5T
|
|
Heat exchanger unit
|
|
|
RDXYQ8T
|
RDXYQ5T
|
Recommended combination 2
|
|
4 x FXSQ50A2VEB
|
SCOP recommended combination 2
|
|
3.5
|
Power input - 50Hz
|
Heating
|
Nom.
|
6°CWB
|
kW
|
|
6.8 (2)
|
3.5 (2)
|
Indoor index connection
|
Min.
|
|
|
100.0
|
62.5
|
|
Max.
|
|
|
260.0
|
162.5
|
Cooling capacity
|
Prated,c
|
kW
|
|
22.4 (1)
|
COP at nom. capacity
|
6°CWB
|
kW/kW
|
|
3.3
|
4.0
|
Recommended combination
|
|
4 x FXMQ50P7VEB
|
4 x FXSQ32A2VEB
|
Space heating (Average climate)
|
TOL
|
COPd (declared COP)
|
|
|
2.0
|
2.2
|
|
|
Pdh (declared heating cap)
|
kW
|
|
12.9
|
10.4
|
|
|
Tol (temperature operating limit)
|
°C
|
|
-10.0
|
-10.0
|
|
D Condition (12°C)
|
Pdh (declared heating cap)
|
kW
|
|
6.0
|
4.1
|
|
|
COPd (declared COP)
|
|
|
7.3
|
5.2
|
|
B Condition (2°C)
|
COPd (declared COP)
|
|
|
3.0
|
3.3
|
|
|
Pdh (declared heating cap)
|
kW
|
|
6.9
|
5.6
|
|
C Condition (7°C)
|
COPd (declared COP)
|
|
|
6.6
|
7.1
|
|
|
Pdh (declared heating cap)
|
kW
|
|
5.4
|
3.6
|
|
A Condition (-7°C)
|
COPd (declared COP)
|
|
|
2.3
|
2.4
|
|
|
Pdh (declared heating cap)
|
kW
|
|
11.4
|
9.2
|
|
TBivalent
|
Pdh (declared heating cap)
|
kW
|
|
12.9
|
10.4
|
|
|
Tbiv (bivalent temperature)
|
°C
|
|
-10.0
|
-10.0
|
|
|
COPd (declared COP)
|
|
|
2.0
|
2.2
|
Piping connections
|
Between Compressor module (CM) and indoor units (IU)
|
Liquid
|
OD
|
mm
|
|
9.52
|
9.52
|
|
|
Gas
|
OD
|
mm
|
|
19.1
|
15.9
|
|
Total piping length
|
System
|
Actual
|
m
|
|
300 (6)
|
140 (6)
|
|
Between Compressor module (CM) and heat exchanger module (HM)
|
Gas
|
OD
|
mm
|
|
22.2
|
19.1
|
|
|
Liquid
|
OD
|
mm
|
|
12.7
|
12.7
|
|
|
Piping length
|
Max.
|
m
|
|
30.0
|
30.0
|
SEER
|
|
4.9
|
5.1
|
Space heating (Average climate) recommended combination 2
|
B Condition (2°C)
|
Pdh (declared heating cap)
|
kW
|
|
6.9
|
|
|
COPd (declared COP)
|
|
|
3.0
|
|
C Condition (7°C)
|
Pdh (declared heating cap)
|
kW
|
|
4.9
|
|
|
COPd (declared COP)
|
|
|
5.9
|
|
A Condition (-7°C)
|
COPd (declared COP)
|
|
|
2.3
|
|
|
Pdh (declared heating cap)
|
kW
|
|
11.4
|
|
D Condition (12°C)
|
Pdh (declared heating cap)
|
kW
|
|
6.0
|
|
|
COPd (declared COP)
|
|
|
7.2
|
|
TBivalent
|
Pdh (declared heating cap)
|
kW
|
|
12.9
|
|
|
COPd (declared COP)
|
|
|
2.0
|
|
|
Tbiv (bivalent temperature)
|
°C
|
|
-10.0
|
Sound power level
|
Cooling
|
Nom.
|
dBA
|
|
81.0 (4)
|
ηs,h
|
%
|
|
140.9
|
Fan
|
External static pressure
|
Max.
|
Pa
|
|
150
|
150
|
Heating capacity
|
Prated,h
|
kW
|
|
12.9
|
|
Nom.
|
6°CWB
|
kW
|
|
22.4 (2)
|
14.0 (2)
|