Specifications Table for UATYA-BFC2Y1

UATYA25BFC2Y1 UATYA30BFC2Y1 UATYA40BFC2Y1 UATYA50BFC2Y1 UATYA60BFC2Y1 UATYA70BFC2Y1 UATYA80BFC2Y1 UATYA90BFC2Y1 UATYA100BFC2Y1 UATYA110BFC2Y1 UATYA120BFC2Y1 UATYA140BFC2Y1 UATYA150BFC2Y1 UATYA160BFC2Y1 UATYA180BFC2Y1 UATYA190BFC2Y1
Cooling capacity Nom. kW         58.8 (1) 65.3 (1)
  With 30% fresh air kW         63.0 (1) 69.9 (1)
Heating capacity Nom. kW         55.1 (2) 64.9 (2)
  With 30% fresh air kW         55.1 (2) 65.1 (2)
Power input Cooling Nom. kW         18.8 (1) 22.4 (1)
  Heating Nom. kW         16.9 (2) 20.2 (2)
EER 2.83 (1), 2.96 (3) 3.09 (1), 3.26 (3) 3.06 (1), 3.21 (3) 2.96 (1), 3.10 (3) 3.12 (1), 3.28 (3) 2.92 (1), 3.06 (3) 3.09 (1), 3.26 (3) 3.06 (1), 3.24 (3) 2.97 (1), 3.13 (3) 2.99 (1), 3.13 (3) 2.91 (1), 3.03 (3) 3.14 (1), 3.29 (3) 3.02 (1), 3.16 (3) 3.05 (1), 3.19 (3) 3.07 (1), 3.21 (3) 2.97 (1), 3.10 (3)
COP 3.22 (2), 3.43 (3) 3.31 (2), 3.53 (3) 3.26 (2), 3.48 (3) 3.24 (2), 3.51 (3) 3.25 (2), 3.47 (3) 3.21 (2), 3.44 (3) 3.37 (2), 3.62 (3) 3.22 (2), 3.47 (3) 3.20 (2), 3.46 (3) 3.35 (2), 3.60 (3) 3.25 (2), 3.48 (3) 3.44 (2), 3.69 (3) 3.33 (2), 3.57 (3) 3.26 (2), 3.50 (3) 3.33 (2), 3.58 (3) 3.27 (2), 3.55 (3)
Space cooling Capacity Pdesign kW         58.8 65.3
  SEER           5.50 (4) 4.53 (4)
Space heating (Average climate) Capacity Pdesign kW         55.1 64.9
  SCOP/A           3.47 (4) 3.41 (4)
Evaporator Supply side Fan Air flow rate m³/h         11,000 13,000
      High ESP Pa         629 (5) 410 (5)
      Nominal ESP Pa         300 (5) 300 (5)
  Fresh air Ratio Standard %         30 30
      In free cooling %         100 100
Operation range Cooling Min. °CDB         -10 -10
    Max. °CDB         48 48
  Heating Min. °CWB         -15 -15
    Max. °CWB         26 26
Condenser Air flow rate Cooling m³/h         31,183 32,203
  Refrigerant GWP           675 675
    Charge kg         18.0 18.0
Dimensions Unit Height mm         1,924 1,924
    Width mm         2,250 2,250
    Depth mm         4,879 4,879
Weight Unit kg         1,703 1,803
Sound pressure level Cooling dBA         69.0 (6) 68.1 (6)
Sound power level Cooling dBA         88.5 (7) 87.5 (7)
Power supply Name           400/3/50±5% 400/3/50±5%
  Phase           3~ 3~
  Frequency Hz         50 50
  Voltage V         400 400
Current Recommended fuses A         50 63
Notes (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 (1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018
  (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 (2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018
  (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air (3) - With 30% fresh air
  (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019 (4) - Calculated according to EN 14825/2019
  (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters. (5) - Value refers to unit at nominal airflow, delivered with no accessories and with only G4 filters.
  (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level (6) - Average sound pressure level, at 1 meter from the unit, in free field on a reflective surface. Not binding value derived from the sound power level
  (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version (7) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version
Operation range Heating Max. °CWB 26 26 26 26     26 26 26 26 26 26 26 26 26 26
    Min. °CWB -15 -15 -15 -15     -15 -15 -15 -15 -15 -15 -15 -15 -15 -15
  Cooling Max. °CDB 48 48 48 48     48 48 48 48 48 48 48 48 48 48
    Min. °CDB -10 -10 -10 -10     -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Cooling capacity Nom. kW 24.1 (1) 31.3 (1) 38.7 (1) 45.7 (1)     74.8 (1) 89.8 (1) 95.8 (1) 108.9 (1) 115.0 (1) 133.4 (1) 144.7 (1) 154.6 (1) 171.9 (1) 187.0 (1)
  With 30% fresh air kW 25.8 (1) 33.6 (1) 41.5 (1) 48.9 (1)     80.7 (1) 96.6 (1) 102.7 (1) 117.0 (1) 122.7 (1) 143.1 (1) 154.9 (1) 165.7 (1) 184.2 (1) 200.5 (1)
Heating capacity Nom. kW 24.0 (2) 29.5 (2) 36.3 (2) 46.2 (2)     68.5 (2) 84.2 (2) 92.8 (2) 101.5 (2) 108.0 (2) 123.1 (2) 136.4 (2) 147.1 (2) 157.1 (2) 176.9 (2)
  With 30% fresh air kW 24.3 (2) 29.6 (2) 36.5 (2) 46.3 (2)     69.2 (2) 84.7 (2) 94.8 (2) 102.1 (2) 108.7 (2) 124.2 (2) 137.5 (2) 148.4 (2) 158.7 (2) 180.2 (2)
Power input Cooling Nom. kW 8.5 (1) 10.1 (1) 12.7 (1) 15.4 (1)     24.2 (1) 29.4 (1) 32.3 (1) 36.4 (1) 39.5 (1) 42.5 (1) 47.9 (1) 50.7 (1) 56.1 (1) 62.9 (1)
  Heating Nom. kW 7.5 (2) 8.9 (2) 11.1 (2) 14.2 (2)     20.3 (2) 26.1 (2) 29.0 (2) 30.3 (2) 33.2 (2) 35.8 (2) 40.9 (2) 45.1 (2) 47.2 (2) 54.2 (2)
Space cooling Capacity Pdesign kW 24.1 31.3 38.7 45.7     74.8 89.8 95.8 108.9 115.0 133.4 144.7 154.6 171.9 187.0
  SEER   4.52 (4) 4.79 (4) 5.39 (4) 5.26 (4)     5.56 (4) 5.47 (4) 5.17 (4) 5.29 (4) 5.15 (4) 4.38 (4) 4.26 (4) 4.27 (4) 4.15 (4) 4.08 (4)
Space heating (Average climate) Capacity Pdesign kW 24.0 29.5 36.3 46.2     68.5 84.2 92.8 101.5 108.0 123.1 136.4 147.1 157.1 176.9
  SCOP/A   3.35 (4) 3.38 (4) 3.67 (4) 3.65 (4)     3.70 (4) 3.65 (4) 3.62 (4) 3.56 (4) 3.53 (4) 3.39 (4) 3.36 (4) 3.34 (4) 3.31 (4) 3.34 (4)
Evaporator Supply side Fan Air flow rate m³/h 4500 5800 7500 9000     14500 16500 18000 19800 21600 25000 26500 28000 30500 31500
      Nominal ESP Pa 300 (5) 300 (5) 300 (5) 300 (5)     300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5) 300 (5)
      High ESP Pa 425 (5) 727 (5) 510 (5) 439 (5)     526 (5) 493 (5) 463 (5) 427 (5) 394 (5) 441 (5) 416 (5) 388 (5) 340 (5) 310 (5)
  Fresh air Ratio Standard % 30 30 30 30     30 30 30 30 30 30 30 30 30 30
      In free cooling % 100 100 100 100     100 100 100 100 100 100 100 100 100 100
Condenser Air flow rate Cooling m³/h 15725 16038 16374 16341     35774 37285 36195 38143 36865 70704 72395 67733 70200 72005
  Refrigerant GWP   675 675 675 675     675 675 675 675 675 675 675 675 675 675
    Charge tCO2Eq 4725 6750 8100 10125     15525 16200 18900 20250 24300 25650 25650 31050 33750 33750
    Charge kg 7.0 10.0 12.0 15.0     23.0 24.0 28.0 30.0 36.0 38.0 38.0 46.0 50.0 50.0
Dimensions Unit Height mm 1924 1924 2374 2374     2374 2374 2374 2374 2374 2374 2374 2374 2374 2374
    Width mm 2250 2250 2250 2250     2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
    Depth mm 2943 2943 2943 2943     4879 4879 4879 4879 4879 5679 5679 5679 5679 5679
Weight Unit kg 981 1014 1084 1143     1984 2040 2110 2196 2206 2658 2668 2708 2746 2828
Sound pressure level Cooling dBA 63.9 (6) 66.0 (6) 68.0 (6) 67.3 (6)     72.6 (6) 68.7 (6) 69.9 (6) 70.6 (6) 74.2 (6) 68.3 (6) 68.3 (6) 68.7 (6) 69.1 (6) 70.0 (6)
Sound power level Cooling dBA 82.2 (7) 84.3 (7) 86.8 (7) 86.1 (7)     92.5 (7) 88.6 (7) 89.8 (7) 90.5 (7) 94.1 (7) 88.6 (7) 88.6 (7) 89.0 (7) 89.3 (7) 90.2 (7)
Power supply Name   400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5%     400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5% 400/3/50±5%
  Phase   3~ 3~ 3~ 3~     3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50     50 50 50 50 50 50 50 50 50 50
  Voltage V 400 400 400 400     400 400 400 400 400 400 400 400 400 400
Current Recommended fuses A 25 40 40 50     80 100 100 100 100 160 160 160 200 200