| VAM150FCVE9 | VAM250FCVE9 | |||||
|---|---|---|---|---|---|---|
| Power input - 50Hz | Heat exchange mode | Nom. | Ultra high | kW | 0.132 | 0.161 |
| Bypass mode | Nom. | Ultra high | kW | 0.132 | 0.161 | |
| Casing | Material | Galvanised steel plate | Galvanised steel plate | |||
| Dimensions | Unit | Height | mm | 285 | 285 | |
| Width | mm | 776 | 776 | |||
| Depth | mm | 525 | 525 | |||
| Weight | Unit | kg | 23 | 23 | ||
| Fan | Air flow rate - 50Hz | Heat exchange mode | Ultra high | m³/h | 150 | 250 |
| Bypass mode | Ultra high | m³/h | 150 | 250 | ||
| External static pressure - 50Hz | Ultra high | Pa | 90.0 | 70.0 | ||
| Operation range | Min. | °CDB | -15 | -15 | ||
| Max. | °CDB | 50 | 50 | |||
| Relative humidity | % | 80 or less | 80 or less | |||
| Sound pressure level - 50Hz | Heat exchange mode | Ultra high | dBA | 27.0 | 28.0 | |
| Bypass mode | Ultra high | dBA | 27.0 | 28.0 | ||
| Heat exchange system | Air to air cross flow total heat (sensible + latent heat) exchange | Air to air cross flow total heat (sensible + latent heat) exchange | ||||
| Heat exchange element | Specially processed non-flammable paper | Specially processed non-flammable paper | ||||
| Connection duct diameter | mm | 100 | 150 | |||
| Operation mode | Heat exchange mode, bypass mode, fresh-up mode | Heat exchange mode, bypass mode, fresh-up mode | ||||
| SEC class | B, See note 4 | B, See note 4 | ||||
| Maximum flow rate at 100 Pa ESP | Flow rate | m³/h | 130 | 207 | ||
| Sound power level (Lwa) | dB | 40 | 43 | |||
| Annual electricity consumption | kWh/a | 771 (4) | 580 (4) | |||
| Annual heating saved | Average climate | kWh/a | 4571 (4) | 4307 (4) | ||
| Cold climate | kWh/a | 8941 (4) | 8426 (4) | |||
| Warm climate | kWh/a | 2067 (4) | 1948 (4) | |||
| Energy Efficiency Range | A+ ~ G | A+ ~ G | ||||
| Power supply | Name | VE | VE | |||
| Phase | 1~ | 1~ | ||||
| Frequency | Hz | 50/60 | 50/60 | |||
| Voltage | V | 220-240/220 | 220-240/220 | |||
| Notes | (1) - Measured on fan curve 15. Refer to fan curves. | (1) - Measured on fan curve 15. Refer to fan curves. | ||||
| (2) - Measured according to JIS B 8628 | (2) - Measured according to JIS B 8628 | |||||
| (3) - Measured at reference flow rate according to EN13141-7 | (3) - Measured at reference flow rate according to EN13141-7 | |||||
| (4) - In accordance with commission regulation (EU) No 1254/2014 | (4) - In accordance with commission regulation (EU) No 1254/2014 | |||||
| (5) - In accordance with commission regulation (EU) No 1253/2014 | (5) - In accordance with commission regulation (EU) No 1253/2014 | |||||
| (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 | (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 | |||||
| (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. | (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. | |||||
| (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (9) - Maximum allowable voltage range variation between phases is 2%. | (9) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) | (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) | |||||
| (11) - Select wire size based on the value of MCA | (11) - Select wire size based on the value of MCA | |||||