Specifications Table for RXYQ-U

RXYQ8U7Y1B RXYQ10U7Y1B RXYQ12U7Y1B RXYQ14U7Y1B RXYQ16U7Y1B RXYQ18U7Y1B RXYQ20U7Y1B RXYQ22U7Y1B RXYQ24U7Y1B RXYQ26U7Y1B RXYQ28U7Y1B RXYQ30U7Y1B RXYQ32U7Y1B RXYQ34U7Y1B RXYQ36U7Y1B RXYQ38U7Y1B RXYQ40U7Y1B RXYQ42U7Y1B RXYQ44U7Y1B RXYQ46U7Y1B RXYQ48U7Y1B RXYQ50U7Y1B RXYQ52U7Y1B RXYQ54U7Y1B
Sound pressure level Cooling Nom. dBA           62.0 (5)   62.5 (5) 64.0 (5) 63.5 (5) 65.1 (5) 64.5 (5) 66.0 (5) 65.5 (5) 67.1 (5) 66.2 (5) 65.2 (5) 66.5 (5) 67.2 (5) 67.0 (5) 67.8 (5) 67.5 (5) 67.1 (5) 66.8 (5)
Standard Accessories Installation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
SEER recommended combination 2 6.9 6.8 5.9 6.3 5.9 6.0 5.9 6.7 6.6 6.5 6.3 6.3 6.3 6.3 6.3 6.8 6.6 6.6 6.3 6.4 6.3 6.3 6.4 6.4
SEER recommended combination 3 7.5 6.8 6.2 6.2 5.8 6.0 5.9 6.9 6.7 6.6 6.4 6.5 6.2 6.3 6.3 6.9 6.7 6.5 6.3 6.3 6.2 6.3 6.4 6.4
Capacity range HP 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
ηs,c recommended combination 2           236.8   266.5 262.6 256.1 249.3 249.8 248.3 250.9 248.7 269.2 259.2 259.3 249.2 252.2 248.3 250.0 251.6 252.5
Operation range Cooling Max. °CDB           43.0
    Min. °CDB           -5.0
  Heating Min. °CWB           -20.0
    Max. °CWB           15.5
ηs,c %           238.3   274.5 269.9 264.2 257.8 256.8 251.7 253.3 250.8 272.4 263.5 261.2 255.9 254.9 251.7 252.8 253.7 254.1
ηs,c recommended combination 3           238.2   273.3 265.3 261.1 253.1 256.1 244.2 249.8 247.2 272.2 263.2 255.4 250.1 248.3 244.2 248.0 251.5 253.9
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3)
Space cooling B Condition (30°C - 27/19) Pdc kW           37.1   45.3 49.7 54.2 57.8 61.8 66.3 70.3 71.5 75.5 82.5 86.9 91.0 95.8 99.5 103.4 107.4 111.4
    EERd             3.8   4.8 4.6 4.6 4.4 4.3 4.3 4.2 4.1 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1
  D Condition (20°C - 27/19) Pdc kW           11.5   18.8 15.8 16.2 16.5 21.0 19.0 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.4
    EERd             18.3   16.0 15.2 14.2 14.3 16.8 14.3 16.8 16.7 17.9 16.0 15.4 14.4 14.3 14.3 15.9 17.6 19.1
  A Condition (35°C - 27/19) EERd             1.9   2.6 2.5 2.6 2.3 2.1 2.3 2.1 2.1 2.4 2.2 2.3 2.3 2.4 2.3 2.1 2.0 1.9
    Pdc kW           50.4   61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd             7.5   8.5 8.6 8.2 8.1 8.2 8.1 8.1 7.9 8.5 8.3 8.2 8.1 8.1 8.1 8.1 8.1 8.1
    Pdc kW           23.9   29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 64.0 66.5 69.1 71.6
SCOP 4.3 4.3 4.1 4.0 4.0 4.2 4.0 4.4 4.3 4.2 4.2 4.3 4.2 4.2 4.1 4.3 4.3 4.2 4.2 4.1 4.1 4.2 4.3 4.3
Compressor Type             Hermetically sealed scroll compressor
Weight Unit kg           308
Refrigerant Charge TCO2Eq           24.4
  GWP             2,087.5   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge kg           11.7
  Type             R-410A   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Space cooling recommended combination 3 B Condition (30°C - 27/19) Pdc kW           37.1   45.3 49.7 54.2 57.8 61.8 66.3 70.3 71.5 75.5 82.5 87.0 91.0 95.8 99.5 103.5 107.4 111.4
    EERd             3.7   4.8 4.5 4.5 4.3 4.3 4.1 4.1 4.0 4.5 4.4 4.3 4.3 4.2 4.1 4.1 4.1 4.1
  D Condition (20°C - 27/19) Pdc kW           11.6   18.8 15.7 16.0 16.6 21.0 19.0 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.7
    EERd             18.3   15.8 15.2 14.0 14.1 16.6 13.8 16.6 16.5 17.9 16.1 15.2 14.2 13.9 13.8 15.6 17.5 19.1
  A Condition (35°C - 27/19) EERd             1.9   2.5 2.5 2.5 2.3 2.1 2.2 2.1 2.1 2.4 2.2 2.3 2.3 2.3 2.2 2.1 2.0 1.9
    Pdc kW           50.4   61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd             7.6   8.5 8.4 8.1 8.0 8.2 7.8 8.0 7.8 8.5 8.4 8.0 7.9 7.9 7.8 7.9 8.0 8.2
    Pdc kW           23.9   29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 63.9 66.5 69.1 71.6
SCOP recommended combination 3 4.2 4.1 4.1 4.0 4.0 4.1 3.9 4.3 4.2 4.2 4.2 4.3 4.1 4.2 4.1 4.2 4.3 4.2 4.2 4.1 4.1 4.2 4.2 4.2
ηs,h recommended combination 2           164.8   172.3 167.1 165.4 166.8 170.6 164.6 167.7 164.1 168.4 171.3 167.3 165.6 163.5 164.3 166.7 168.7 170.8
ηs,h recommended combination 3           159.6   170.2 165.5 164.5 165.0 167.0 161.9 164.2 159.9 164.8 167.8 164.4 163.5 161.3 161.7 163.2 164.4 166.0
Space cooling recommended combination 2 C Condition (25°C - 27/19) Pdc kW           23.9   29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 63.9 66.5 69.0 71.6
    EERd             7.5   8.2 8.4 7.9 7.8 7.9 8.0 8.1 7.9 8.4 8.1 8.2 7.9 8.1 8.0 8.0 8.1 8.1
  A Condition (35°C - 27/19) EERd             1.9   2.6 2.4 2.6 2.3 2.1 2.2 2.1 2.1 2.3 2.2 2.3 2.3 2.3 2.2 2.1 2.0 1.9
    Pdc kW           50.4   61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  D Condition (20°C - 27/19) EERd             18.1   15.6 14.7 13.6 13.8 16.1 14.0 16.5 16.5 17.8 15.9 15.3 14.0 14.0 14.0 15.6 17.4 18.9
    Pdc kW           11.4   18.4 15.4 15.7 16.5 20.5 18.9 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.1
  B Condition (30°C - 27/19) EERd             3.7   4.6 4.5 4.4 4.3 4.2 4.2 4.2 4.1 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.1
    Pdc kW           37.1   45.3 49.7 54.1 57.8 61.8 66.3 70.3 71.5 75.4 82.4 86.9 91.0 95.8 99.5 103.5 107.4 111.4
System Outdoor unit module 2                 RXYQ12U RXYQ16U RXYQ14U RXYQ16U RXYQ18U RXYQ16U RXYQ18U RXYQ20U RXYQ10U RXYQ12U RXYQ16U RXYQ16U RXYQ16U RXYQ16U RXYQ16U RXYQ18U RXYQ18U
  Outdoor unit module 3                                 RXYQ20U RXYQ18U RXYQ16U RXYQ16U RXYQ16U RXYQ16U RXYQ18U RXYQ18U RXYQ18U
  Outdoor unit module 1                 RXYQ10U RXYQ8U RXYQ12U RXYQ12U RXYQ12U RXYQ16U RXYQ16U RXYQ16U RXYQ8U RXYQ10U RXYQ10U RXYQ12U RXYQ14U RXYQ16U RXYQ16U RXYQ16U RXYQ18U
Recommended combination 3 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 2 x FXMQ50P7VEB + 6 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 9 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB 9 x FXMQ50P7VEB + 9 x FXMQ63P7VEB 12 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 1 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 12 x FXMQ63P7VEB + 6 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 14 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 15 x FXMQ63P7VEB
Recommended combination 2 4 x FXSQ50A2VEB 4 x FXSQ63A2VEB 6 x FXSQ50A2VEB 1 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB 4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 7 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 9 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 2 x FXSQ50A2VEB + 10 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 10 x FXSQ63A2VEB 9 x FXSQ50A2VEB + 9 x FXSQ63A2VEB 12 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 1 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 12 x FXSQ63A2VEB + 6 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 14 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 15 x FXSQ63A2VEB
SCOP recommended combination 2 4.2 4.3 4.1 4 4.1 4.2 4 4.4 4.3 4.2 4.2 4.3 4.2 4.3 4.2 4.3 4.4 4.3 4.2 4.2 4.2 4.2 4.3 4.3
Power input - 50Hz Heating Nom. 6°CWB kW           14.22 (2)   17.23 (2) 17.94 (2) 20.33 (2) 22.19 (2) 23.87 (2) 25.08 (2) 26.76 (2) 30.02 (2) 30.45 (2) 31.45 (2) 32.66 (2) 34.73 (2) 35.77 (2) 37.62 (2) 39.30 (2) 40.98 (2) 42.66 (2)
Indoor index connection Min.             225.0   275.0 300.0 325.0 350.0 375.0 400.0 425.0 450.0 475.0 500.0 525.0 550.0 575.0 600.0 625.0 650.0 675.0
  Max.             585.0   715.0 780.0 845.0 910.0 975.0 1,040.0 1,105.0 1,170.0 1,235.0 1,300.0 1,365.0 1,430.0 1,495.0 1,560.0 1,625.0 1,690.0 1,755.0
Cooling capacity Prated,c kW           50.4 (1)   61.5 (1) 67.4 (1) 73.5 (1) 78.5 (1) 83.9 (1) 90.0 (1) 95.4 (1) 97.0 (1) 102.4 (1) 111.9 (1) 118.0 (1) 123.5 (1) 130.0 (1) 135.0 (1) 140.4 (1) 145.8 (1) 151.2 (1)
COP at nom. capacity 6°CWB kW/kW           3.54 (2)   3.57 (2) 3.76 (2) 3.61 (2) 3.54 (2) 3.51 (2) 3.59 (2) 3.56 (2) 3.36 (2) 3.49 (2) 3.56 (2) 3.61 (2) 3.56 (2) 3.63 (2) 3.59 (2) 3.57 (2) 3.56 (2) 3.54 (2)
Recommended combination 4 x FXFQ50AVEB 4 x FXFQ63AVEB 6 x FXFQ50AVEB 1 x FXFQ50AVEB + 5 x FXFQ63AVEB 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 3 x FXFQ50AVEB + 5 x FXFQ63AVEB 2 x FXFQ50AVEB + 6 x FXFQ63AVEB 6 x FXFQ50AVEB + 4 x FXFQ63AVEB 4 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 7 x FXFQ50AVEB + 5 x FXFQ63AVEB 6 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 9 x FXFQ50AVEB + 5 x FXFQ63AVEB 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 3 x FXFQ50AVEB + 9 x FXFQ63AVEB + 2 x FXFQ80AVEB 2 x FXFQ50AVEB + 10 x FXFQ63AVEB + 2 x FXFQ80AVEB 6 x FXFQ50AVEB + 10 x FXFQ63AVEB 9 x FXFQ50AVEB + 9 x FXFQ63AVEB 12 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 1 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 12 x FXFQ63AVEB + 6 x FXFQ80AVEB 3 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 14 x FXFQ63AVEB + 2 x FXFQ80AVEB 9 x FXFQ50AVEB + 15 x FXFQ63AVEB
Space heating (Average climate) TOL COPd (declared COP)             1.9   2.3 2.5 2.3 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Pdh (declared heating cap) kW           27.9   34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C           -10   -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW           7.1   6.0 5.7 6.0 6.4 7.1 7.1 7.9 8.3 13.1 13.1 9.9 10.0 10.3 10.7 12.0 14.2 14.2
    COPd (declared COP)             9.0   8.2 8.9 8.8 9.0 9.0 9.0 8.8 8.6 8.7 8.7 8.6 8.6 8.7 8.8 8.9 9.0 9.0
  B Condition (2°C) COPd (declared COP)             3.7   4.0 3.7 3.8 3.8 3.9 3.6 3.7 3.7 3.9 4.0 3.7 3.7 3.6 3.6 3.7 3.8 3.9
    Pdh (declared heating cap) kW           15.0   18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
  C Condition (7°C) COPd (declared COP)             6.7   6.3 6.3 6.1 6.2 6.5 6.3 6.5 6.4 6.5 6.5 6.3 6.3 6.2 6.3 6.5 6.6 6.8
    Pdh (declared heating cap) kW           9.7   11.9 13.0 13.5 14.4 16.0 16.1 17.7 18.8 21.3 21.6 21.6 22.4 23.2 24.1 25.7 27.4 29.0
  A Condition (-7°C) COPd (declared COP)             2.4   2.6 2.8 2.6 2.6 2.6 2.7 2.6 2.5 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.6 2.6
    Pdh (declared heating cap) kW           24.7   30.4 32.6 34.5 36.8 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
  TBivalent Pdh (declared heating cap) kW           27.9   34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tbiv (bivalent temperature) °C           -10   -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)             1.9   2.3 2.5 2.3 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
Piping connections Liquid OD mm           15.9   15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
    Type             Braze connection   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Total piping length System Actual m           1,000 (6)   1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6)
  Gas OD mm           28.6   28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3
    Type             Braze connection   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
SEER 7.6 6.8 6.3 6.3 6.0 6.0 5.9 6.9 6.8 6.7 6.5 6.5 6.4 6.4 6.3 6.9 6.7 6.6 6.5 6.4 6.4 6.4 6.4 6.4
Space heating (Average climate) recommended combination 2 B Condition (2°C) Pdh (declared heating cap) kW           15.0   18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.6 45.1
    COPd (declared COP)             3.8   4.1 3.7 3.8 3.8 3.9 3.6 3.8 3.7 3.9 4.0 3.7 3.7 3.6 3.6 3.7 3.8 3.9
  C Condition (7°C) Pdh (declared heating cap) kW           9.7   11.9 13.1 13.1 14.4 16.0 16.1 17.7 18.8 21.3 21.6 21.6 22.4 22.8 24.1 25.7 27.4 29.0
    COPd (declared COP)             6.8   6.3 6.3 6.1 6.3 6.6 6.3 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.3 6.5 6.7 6.8
  A Condition (-7°C) COPd (declared COP)             2.4   2.6 2.7 2.6 2.6 2.6 2.7 2.6 2.5 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.6 2.6
    Pdh (declared heating cap) kW           24.7   30.4 32.6 34.5 36.8 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
  TOL Pdh (declared heating cap) kW           27.9   34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)             1.9   2.2 2.4 2.2 2.2 2.1 2.4 2.2 2.2 2.3 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Tol (temperature operating limit) °C           -10   -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW           7.2   6.0 5.7 6.0 6.4 7.2 7.1 7.9 8.3 13.2 13.2 10.0 10.0 10.3 10.7 12.2 14.4 14.4
    COPd (declared COP)             9.1   8.4 9.0 8.9 9.1 9.1 9.1 8.9 8.8 8.8 8.8 8.7 8.7 8.8 8.9 9.0 9.1 9.1
  TBivalent Pdh (declared heating cap) kW           27.9   34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)             1.9   2.2 2.4 2.2 2.2 2.1 2.4 2.2 2.2 2.3 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Tbiv (bivalent temperature) °C           -10   -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Space heating (Average climate) recommended combination 3 B Condition (2°C) Pdh (declared heating cap) kW           15.0   18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
    COPd (declared COP)             3.7   4.0 3.7 3.8 3.8 3.9 3.6 3.7 3.6 3.8 3.9 3.7 3.7 3.6 3.6 3.6 3.7 3.8
  C Condition (7°C) COPd (declared COP)             6.5   6.2 6.3 6.1 6.2 6.3 6.3 6.4 6.3 6.3 6.4 6.3 6.2 6.2 6.3 6.4 6.4 6.5
    Pdh (declared heating cap) kW           9.7   11.9 12.9 13.5 14.4 16.0 16.1 17.7 18.8 21.2 21.6 21.6 22.4 23.2 24.1 25.7 27.3 29.0
  A Condition (-7°C) Pdh (declared heating cap) kW           24.7   30.4 32.6 34.5 36.8 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
    COPd (declared COP)             2.4   2.6 2.7 2.6 2.6 2.5 2.7 2.6 2.4 2.5 2.6 2.7 2.6 2.7 2.7 2.6 2.6 2.5
  TOL Pdh (declared heating cap) kW           27.9   34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C           -10   -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)             1.9   2.3 2.4 2.2 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.2 2.2 2.1
  D Condition (12°C) COPd (declared COP)             8.7   8.2 8.9 8.8 9.0 8.6 9.0 8.9 8.3 8.5 8.4 8.6 8.6 8.7 8.8 8.7 8.7 8.7
    Pdh (declared heating cap) kW           6.9   6.0 5.7 6.0 6.4 7.1 7.1 7.9 8.3 12.9 12.8 9.9 10.0 10.3 10.7 11.8 13.7 13.7
  TBivalent Pdh (declared heating cap) kW           27.9   34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)             1.9   2.3 2.4 2.2 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.2 2.2 2.1
    Tbiv (bivalent temperature) °C           -10   -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Sound power level Cooling Nom. dBA           83.8 (4)   84.8 (4) 86.3 (4) 85.3 (4) 87.6 (4) 86.6 (4) 88.6 (4) 87.8 (4) 89.9 (4) 88.8 (4) 87.3 (4) 89.1 (4) 89.8 (4) 89.3 (4) 90.4 (4) 89.8 (4) 89.3 (4) 88.6 (4)
Dimensions Unit Width mm           1,240
    Depth mm           765
    Height mm           1,685
ηs,h %           163.1   171.2 167.0 164.6 166.0 169.8 163.1 166.2 162.4 167.5 170.0 165.5 164.5 162.0 162.8 165.2 167.2 169.4
Fan External static pressure Max. Pa           78
Heating capacity Prated,h kW           50.4 (2)   61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
  Nom. 6°CWB kW           50.4 (2)   61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
Power supply Phase             3N~   3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
  Name             Y1   Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Frequency Hz           50   50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V           380-415   380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - FLA means the nominal running current of the fan (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
            (12) - FLA means the nominal running current of the fan   (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan
            (13) - Maximum allowable voltage range variation between phases is 2%.   (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%.
            (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.   (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
            (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )   (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )
            (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality   (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
            (17) - Sound values are measured in a semi-anechoic room.   (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room.
            (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA   (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
            (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase   (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
            (20) - Ssc: Short-circuit power   (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power
            (21) - For detailed contents of standard accessories, see installation/operation manual   (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual
            (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination   (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination
Cooling capacity Prated,c kW 22.4 (1) 28 33.5 (1) 40 45   52
Heating capacity Prated,h kW 22.4 (2) 28 33.5 (2) 40 45   56
  Nom. 6°CWB kW 22.4 (2) 28 33.5 (2) 40 45   56
COP at nom. capacity 6°CWB KW/KW 4.15 (2) 3.69 (2) 3.47 (2) 3.74 (2) 3.59 (2)   3.2
Space cooling A Condition (35°C - 27/19) EERd   3.0 2.3 2.4 2.6 2.1   1.9
    Pdc kW 22.4 28.0 33.5 40.0 45.0   52.0
  B Condition (30°C - 27/19) EERd   5.2 4.7 4.3 4.1 3.9   3.7
    Pdc kW 16.5 20.6 24.7 29.5 33.2   38.3
  C Condition (25°C - 27/19) EERd   9.5 8.3 7.7 7.8 7.7   7.3
    Pdc kW 10.6 13.3 15.9 18.9 21.3   24.6
  D Condition (20°C - 27/19) EERd   18.8 17.0 13.9 14.3 14.2   18.3
    Pdc kW 8.0 9.3 9.4 8.4 9.5   11.5
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd   2.6 2.4 2.4 2.6 2.1   1.9
    Pdc kW 22.4 28 33.5 40 45   52
  B Condition (30°C - 27/19) EERd   4.9 4.7 4 4.1 3.8   3.6
    Pdc kW 16.5 20.6 24.7 29.5 33.2   38.3
  C Condition (25°C - 27/19) EERd   8.8 8.5 7.1 7.9 7.6   7.3
    Pdc kW 10.6 13.3 15.9 18.9 21.3   24.6
  D Condition (20°C - 27/19) EERd   15.1 17.2 13.1 14 14   18.9
    Pdc kW 8.8 9.3 9.1 8.4 9.5   10.9
Space cooling recommended combination 3 A Condition (35°C - 27/19) EERd   3.0 2.3 2.4 2.6 2.1   1.9
    Pdc kW 22.4 28.0 33.5 40.0 45.0   52.0
  B Condition (30°C - 27/19) EERd   5.1 4.7 4.2 4.0 3.7   3.6
    Pdc kW 16.5 20.6 24.7 29.5 33.2   38.3
  C Condition (25°C - 27/19) EERd   9.6 8.4 7.7 7.7 7.4   7.3
    Pdc kW 10.6 13.3 15.9 19.0 21.3   24.6
  D Condition (20°C - 27/19) EERd   16.0 16.9 13.7 14.0 14.1   18.3
    Pdc kW 9.1 9.3 9.4 8.4 9.5   11.6
Space heating (Average climate) TBivalent COPd (declared COP)   2.5 2.4 2.0 2.3 2.2   1.8
    Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2   31.0
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10   -10
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)   2.5 2.4 2.0 2.3 2.2   1.8
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW 13.7 16.0 18.4 20.6 23.2   31.0
  TOL Tol (temperature operating limit) °C -10 -10 -10 -10 -10   -10
  A Condition (-7°C) COPd (declared COP)   2.7 2.6 2.4 2.6 2.6   2.1
    Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5   27.4
  B Condition (2°C) COPd (declared COP)   3.9 3.9 3.9 3.5 3.5   3.6
    Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5   16.7
  C Condition (7°C) COPd (declared COP)   6.3 6.4 6.1 6.1 6.3   6.5
    Pdh (declared heating cap) kW 5.0 5.5 6.4 7.1 8.0   10.7
  D Condition (12°C) COPd (declared COP)   7.9 8.2 7.9 8.5 8.6   9.1
    Pdh (declared heating cap) kW 5.9 5.9 6.3 4.9 4.9   7.1
Space heating (Average climate) recommended combination 2 TBivalent COPd (declared COP)   2.4 2.4 1.9 2.3 2.2   1.8
    Pdh (declared heating cap) kW 13.7 16 18.4 20.6 23.2   31
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10   -10
  TOL COPd (declared COP)   2.4 2.4 1.9 2.3 2.2   1.8
    Pdh (declared heating cap) kW 13.7 16 18.4 20.6 23.2   31
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10   -10
  A Condition (-7°C) COPd (declared COP)   2.7 2.7 2.4 2.6 2.6   2.2
    Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5   27.4
  B Condition (2°C) COPd (declared COP)   3.9 4 3.9 3.5 3.5   3.7
    Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.2   16.7
  C Condition (7°C) COPd (declared COP)   6.3 6.5 6.1 6.1 6.3   6.5
    Pdh (declared heating cap) kW 5 5.5 6.4 7.1 8   10.7
  D Condition (12°C) COPd (declared COP)   7.8 8.3 7.9 8.6 8.7   9.2
    Pdh (declared heating cap) kW 5.9 6 6.4 4.9 5   7.2
Space heating (Average climate) recommended combination 3 TBivalent COPd (declared COP)   2.5 2.4 2.0 2.3 2.2   1.8
    Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2   31.0
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10   -10
  TOL COPd (declared COP)   2.5 2.4 2.0 2.3 2.2   1.8
    Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2   31.0
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10   -10
  A Condition (-7°C) COPd (declared COP)   2.7 2.6 2.4 2.6 2.6   2.1
    Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5   27.4
  B Condition (2°C) COPd (declared COP)   3.9 3.7 3.9 3.5 3.5   3.6
    Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5   16.7
  C Condition (7°C) COPd (declared COP)   6.2 6.4 6.0 6.1 6.2   6.3
    Pdh (declared heating cap) kW 4.9 5.5 6.4 7.1 8.0   10.7
  D Condition (12°C) COPd (declared COP)   7.8 8.1 7.8 8.5 8.6   8.7
    Pdh (declared heating cap) kW 5.8 5.9 6.2 4.9 4.9   6.9
Indoor index connection Min.   100 125 150 175 200   250
  Max.   260 325 390 455 520   650
Dimensions Unit Height mm 1,685 1,685 1,685 1,685 1,685   1,685
    Width mm 930 930 930 1,240 1,240   1,240
    Depth mm 765 765 765 765 765   765
Weight Unit kg 198 198 198 275 275   308
Fan External static pressure Max. Pa 78 78 78 78 78   78
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor   Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5 -5 -5 -5 -5   -5
    Max. °CDB 43 43 43 43 43   43
  Heating Min. °CWB -20 -20 -20 -20 -20   -20
    Max. °CWB 15.5 15.5 15.5 15.5 15.5   15.5
Sound power level Cooling Nom. dBA 78.0 (4) 79.1 (4) 83.4 (4) 80.9 (4) 85.6 (4)   87.9 (4)
Sound pressure level Cooling Nom. dBA 57 57 61 60 63   65
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A   R-410A
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5   2,087.5
  Charge tCO2Eq 12.3 12.5 13.2 21.5 23.6   24.6
  Charge kg 5.9 6 6.3 10.3 11.3   11.8
Piping connections Liquid Type   Braze connection Braze connection Braze connection Braze connection Braze connection   Braze connection
    OD mm 9.52 9.52 12.7 12.7 12.7   15.9
  Gas Type   Braze connection Braze connection Braze connection Braze connection Braze connection   Braze connection
    OD mm 19.1 22.2 28.6 28.6 28.6   28.6
  Total piping length System Actual m 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6)   1,000 (6)
Power supply Name   Y1 Y1 Y1 Y1 Y1   Y1
  Phase   3N~ 3N~ 3N~ 3N~ 3N~   3N~
  Frequency Hz 50 50 50 50 50   50
  Voltage V 380-415 380-415 380-415 380-415 380-415   380-415