Specifications Table for RQEQ-P3

RQEQ140PY13 RQEQ180PY13 RQEQ212PY13
Cooling capacity Prated,c kW 14.0 18.0 20.0
  Nom. kW 14.0 (1) 18.0 (1) 21.2 (1)
Heating capacity Prated,h kW 16.0 20.0 22.4
  Nom. kW 16.0 (2) 20.0 (2) 22.4 (2)
Space cooling A Condition (35°C - 27/19) EERd   2.54 2.22 1.74
    Pdc kW 14.0 18.0 20.0
  B Condition (30°C - 27/19) EERd   4.40 3.86 3.63
    Pdc kW 10.3 13.3 14.7
  C Condition (25°C - 27/19) EERd   7.31 6.89 6.57
    Pdc kW 6.63 8.53 9.47
  D Condition (20°C - 27/19) EERd   9.29 9.54 9.64
    Pdc kW 5.01 4.94 4.95
Space heating (Average climate) TBivalent COPd (declared COP)   1.92 1.84 1.64
    Pdh (declared heating cap) kW 8.5 10.6 11.9
    Tbiv (bivalent temperature) °C -10 -10 -10
  TOL COPd (declared COP)   1.92 1.84 1.64
    Pdh (declared heating cap) kW 8.5 10.6 11.9
  A Condition (-7°C) COPd (declared COP)   2.20 2.22 2.20
    Pdh (declared heating cap) kW 7.52 9.40 10.5
  B Condition (2°C) COPd (declared COP)   3.42 3.56 3.92
    Pdh (declared heating cap) kW 4.58 5.72 6.41
  C Condition (7°C) COPd (declared COP)   4.84 5.26 5.40
    Pdh (declared heating cap) kW 3.29 3.68 4.12
  D Condition (12°C) COPd (declared COP)   6.43 6.82 6.88
    Pdh (declared heating cap) kW 4.18 4.40 4.44
Dimensions Unit Height Mm 1,680 1,680 1,680
    Width Mm 635 635 635
    Depth Mm 765 765 765
Weight Unit kg 175 175 179
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5 -5 -5
    Max. °CDB 43 43 43
  Heating Min. °CWB -20 -20 -20
    Max. °CWB 15.5 15.5 15.5
Sound power level Cooling Nom. dBA 79 83 87
Refrigerant Type   R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5
  Charge kg 10.3 10.6 11.2
  Charge TCO2Eq 21.5 22.1 23.4
Piping connections Liquid Type   Braze connection Braze connection Braze connection
    OD Mm 9.52 9.52 9.52
  Gas Type   Braze connection Braze connection Braze connection
    OD Mm 15.9 19.1 19.1
  Discharge gas OD Mm 12.7 15.9 15.9
    Type   Braze connection Braze connection Braze connection
Power supply Name   Y1 Y1 Y1
  Phase   3~ 3~ 3~
  Frequency Hz 50 50 50
  Voltage V 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
  (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (5) - TOCA means the total value of each OC set. (5) - TOCA means the total value of each OC set. (5) - TOCA means the total value of each OC set.
  (6) - MSC means the maximum current during start up of the compressor (6) - MSC means the maximum current during start up of the compressor (6) - MSC means the maximum current during start up of the compressor
  (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%.
  (9) - Select wire size based on the larger value of MCA or TOCA (9) - Select wire size based on the larger value of MCA or TOCA (9) - Select wire size based on the larger value of MCA or TOCA
  (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases